PENGARUH GANGGUAN PARTIAL DISCHARGE SKTM 20 KV TERHADAP KEANDALAN PENYULANG DI PT PLN (PERSERO) UP3 LENTENG AGUNG

SIMANGUNSONG, DARWIN PATAR and Diantari, Retno Aita (2022) PENGARUH GANGGUAN PARTIAL DISCHARGE SKTM 20 KV TERHADAP KEANDALAN PENYULANG DI PT PLN (PERSERO) UP3 LENTENG AGUNG. Diploma thesis, ITPLN.

[thumbnail of PROYEK AKHIR_DARWIN PATAR SIMANGUNSONG_201971_DARWIN PATAR SIMANGU.pdf] Text
PROYEK AKHIR_DARWIN PATAR SIMANGUNSONG_201971_DARWIN PATAR SIMANGU.pdf
Restricted to Registered users only

Download (3MB)

Abstract

Partial discharge merupakan suatu gangguan berupa gejala lepasnya muatan (discharge) yang terjadi di salah satu atau beberapa bagian dari suatu sistem isolasi dan bersifat setempat (Lokal). Gangguan partial discharge dapat dilakukan pengujian untuk melihat baik buruk nya pelepasan muatan pada SKTM yang terindikasi partial discharge. Diantara nya inspeksi sistem kabel dan PD mapping. Banyaknya gangguan partial discharge pada SKTM terjadi dikarenakan oleh jointing yang buruk atau dampak lain seperti kerukan pada kabel yang menyebabkan rongga (void).penelitian yang dilakukan bertempat pada Unit pelayanan pelanggan Lenteng Agung yang memiliki beberapa gangguan yang diantaranya didominasi oleh gangguan partial discharge pada jointing Penelitian ini bertujuan untuk mengetahui pengaruh dari pada gangguan partial discharge terhadap keandalan penyulang UP3 lenteng agung dan memahami pengujian dan nilai perhitungan Partial discharge (PD) dengan parameter PDmax [pC] dan PDLevel [pC]. Metode analisis yang digunakan pada penelitian ini yaitu metode analisis kuantitatif. Dengan metode pengujian untuk pengumpulan data yang dilakukan adalah metode assessment kabel 20 kV. Hasil penelitian menunjukan bahwa partial discharge merupakan gangguan yang paling sering terjadi dan berpengaruh pada keandalan penyulang dengan 9 gangguan yang disebabkan oleh partial discharge pada jointing. dan hasil analisis kondisi kabel penyulang Mertua bersatus waspada dengan estimasi pemeliharaan 1 Tahun dengan kesimpulan analisi berdasarkan pelepasan tegangan PDIV dan PDEV dan pelepasan muatan pada kabel nya sebesar dan kondisi penyulang Rebana berstatus buruk dengan estimasi pemeliharaan 6 bulan.

Partial discharge is a disturbance in the form of discharge symptoms that occur in one or several parts of an isolation system and are local (local). Partial discharge disturbances can be tested to see whether the discharge is good or bad on the SKTM which is indicated by partial discharge. Among them are cable system inspections and PD mapping. The number of partial discharge disturbances in SKTM occurs due to poor jointing or other impacts such as dredging of the cable which causes voids. The research was conducted at the Lenteng Agung customer service unit which had several disturbances which were dominated by partial discharge disturbances in jointing. This study aims to determine the effect of partial discharge disturbance on the reliability of the UP3 Lenteng Agung feeder and to understand the test and calculation value of Partial discharge (PD) with parameters PDmax [pC] and PDLevel [pC]. The analytical method used in this research is quantitative analysis method. The test method for data collection is the 20 kV cable assessment method. The results showed that partial discharge is the most frequent disturbance and affects the reliability of the feeder with 9 disturbances caused by partial discharge in the jointing. and the results of the analysis of the condition of the Mertua feeder cable being alert with an estimated maintenance of 1 year with the conclusion of the analysis based on the PDIV and PDEV voltage discharges and the discharge of the load on the cable as large as and the condition of the Tambourine feeder in poor status with an estimated maintenance of 6 months.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: SKTM, partial discharge fault, reliability. SKTM, gangguan partial discharge, keandalan.
Subjects: Skripsi
Bidang Keilmuan > Teknik Tenaga Listrik
Divisions: Vokasi > D3 Teknologi Listrik
Depositing User: Sudarman
Date Deposited: 20 Apr 2026 02:51
Last Modified: 20 Apr 2026 02:51