Genys, Akhal Qaida and Azzahra, Septianissa (2022) KAJIAN PENGARUH KANDUNGAN AIR DAN TEMPERATUR TERHADAP NILAI TEGANGAN TEMBUS MINYAK TRANSFORMATOR DISTRIBUSI PDI PT. PLN (PERSERO) UP3 (Unit Pelaksana Pelayanan Pelanggan) TELUK NAGA. Diploma thesis, ITPLN.
PROYEK AKHIR_AKHAL QAIDA GENYS_201971121_AKHAL QAIDA GENYS.pdf
Restricted to Registered users only
Download (3MB)
Abstract
Pada penelitian ini akan membahas tentang bagaimana pengaruh kadar air dan pengaruh temperature suhu terhadap nilai dari tegangan tembus pada minyak transformator distribusi yang mana apakah bila diberi kadar air yang sudah di tentukan akan berpenaruh terhadap nilai dari kinerja daripada transformator tersebut. Beberapa pengujian yang dilakukan dalam rangka menjaga performa minyak transformator tetap optimal diantaranya adalah pengujian tegangan tembus atau biasa disebut Break Down Voltage test disingkat BDV. Pengujian tegangan tembus bertujuan untuk mengetahui batas maksimal tegangan yang dapat diatasi oleh minyak transformator sebelum akhirnya break down atau tembus. Pada hasil pengujian kenaikan yang tertinggi terjadi pada suhu 45 °C dengan nilai kenaikan nya yaitu sebesar 6,19 kV sedangkan pada hasil pengujian pengaruh kadar air terhadap tegangan tembus dari hasil tersebut terlihat bahwa semakin tinggi jumlah air yang terkandung dalam objek uji maka tegangan tembus yang didapatkan maka akan semakin rendah, pada data tabel nilai tegangan tembus yang tertinggi terdapat pada minyak yang memiliki kandungan air 0 ml dengan nilai 25,73 kV, sedangkan nilai tegangan tembus terendah yang memiliki nilai kandungan air sebesar 12ml dengan nilai tegangan 15,81 kV
In this study, we will discuss how the influence of water content and the effect of temperature on the value of the breakdown voltage on distribution transformer oil will affect the value of the performance of the transformer. Several tests were carried out in order to maintain optimal performance of transformer oil, including the breakdown voltage test or commonly called the Break Down Voltage test, abbreviated as BDV. The breakdown voltage test aims to determine the maximum voltage limit that can be overcome by transformer oil before it finally breaks down. In the test results, the highest increase occurred at a temperature of 45 °C with an increase value of 6.19 kV while the results of testing the effect of water content on the breakdown voltage from these results showed that the higher the amount of water contained in the test object, the higher the breakdown voltage. obtained it will be lower, in the table data the highest breakdown voltage value is found in oil which has a water content of 0 ml with a value of 25.73 kV, while the lowest breakdown voltage value has a water content value of 12 ml with a voltage value of 15.81 Kv.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Transformator, Tegangan tembus, Minyak Transformator Transformer, Breakout Voltage, Transformer Oil |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Tenaga Listrik |
| Divisions: | Vokasi > D3 Teknologi Listrik |
| Depositing User: | Sudarman |
| Date Deposited: | 20 Apr 2026 04:23 |
| Last Modified: | 20 Apr 2026 04:23 |
| URI: | https://repository.itpln.ac.id/id/eprint/6441 |