RAMDHAN, AGUS and handayani, oktaria (2022) PENGARUH SUHU TERHADAP RUGI-RUGI KORONA PADA GARDU DISTRIBUSI BTRY, BTRB, DAN BTTI DI PT.PLN ( PERSERO ) UP3 BEKASI. Diploma thesis, ITPLN.
PROYEK AKHIR_AGUS RAMDHAN_201971091_AGUS RAMDHAN.pdf
Restricted to Registered users only
Download (2MB)
Abstract
Pada penelitian ini bertujuan untuk mengetahui seberapa pengaruh suhu terhadap gangguan korona pada gardu distribusi dan besar rugi-rugi dayanya . Perlengkapan hubung tegangan menengah 20 kV gardu distribusi pasangan dalam adalah kubikel. Tegangan kerja PLN di sisi distribusi satu fasa adalah 11,56kV. Dengan semakin tingginya tegangan maka timbul persoalan isolasi pada peralatan di dalam kubikel. Persoalan yang sering terjadi di kubikel saat ini adalah korona, yaitu suatu fenomena yang terjadi pada saat udara di sekitar konduktor atau penghantar terionisasi. Dari proses tersebut terjadilah pelepasan muatan yang dapat mengakibatkan kegagalan isolasi pada udara. Pengaruh suhu terhadap rugi-rugi korona maka dapat dianalisa indikasi terjadi atau tidak terjadi korona pada kubikel. Dari data gardu yang digunakan, maka dapat dihitung besarnya rugi-rugi daya akibatnya fatal karena bisa menimbulkan kerusakan fisik pada peralatan di dalam kubikel, menyebabkan audio noise dan rugi–rugi daya. Hasil ukur yang didapatkan pada gardu BTRY nilai suhu nya 32ᵒC menghasilkan rugi rugi daya 4,725 kW, kemudian pada gardu BTRB nilai suhunya 35ᵒC menghasilkan rugi-rugi daya 2,554 kW, dan pada gardu BTTI nilai suhunya 31ᵒC menghasilkan rugi rugi daya 6,566 kW.
This study aims to determine the effect of temperature on corona disturbances at distribution substations and the magnitude of the power losses. The 20 kV medium voltage connection equipment in the inner pair distribution substation is a cubicle. The PLN working voltage on the single-phase distribution side is 11.56kV. With the higher the voltage, the insulation problem arises in the equipment in the cubicle. The problem that often occurs in cubicles today is the corona, which is a phenomenon that occurs when the air around the conductor or conductor is ionized. From this process there is a discharge that can result in the failure of the insulation in the air. The effect of temperature on corona losses can then be analyzed for indications of whether or not there is a corona in the cubicle. From the data of the substation used, it can be calculated the magnitude of the power losses, the consequences of which are fatal because they can cause physical damage to the equipment in the cubicle, causing audio noise and power losses. The measurement results obtained at the BTRY substation have a temperature value of 32ᵒC resulting in a power loss of 4,725 kW, then at the BTRB substation the temperature value is 35ᵒC resulting in a power loss of 2,554 kW, and at the BTTI substation the temperature value is 31ᵒC resulting in a power loss of 6,566 kW.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Suhu, Kubikel, Tegangan Pemunculan, dan Korona. Temperature, Cubicles , Generating Voltage, and Corona |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Tenaga Listrik |
| Divisions: | Vokasi > D3 Teknologi Listrik |
| Depositing User: | Sudarman |
| Date Deposited: | 20 Apr 2026 04:39 |
| Last Modified: | 20 Apr 2026 04:39 |
| URI: | https://repository.itpln.ac.id/id/eprint/6443 |