Abstract

Dalam penyaluran tenaga listrik pada gardu induk, gardu distribusi, gardu hubung khususnya jaringan 20 kv sering terjadi gangguan. Dampak terjadinya korona pada kubikel 20 kv yaitu terjadinya tegangan tidak stabil, rugi-rugi daya serta kegagalan isolasi yang dapat menyebabkan pengaruh penurunan kualitas penyaluran tenaga listrik pada konsumen. Penelitian ini bertujuan untuk mengetahui hal yang dapat menyebabkan terdapatnya korona pada kubikel, untuk mengetahui rugi-rugi daya yang diakibatkan oleh korona serta mengetahui cara untuk mengatasi gangguan korona terhadap kubikel. Metode penelitian yang digunakan pada penelitian ini yaitu dengan deskriptif kuantitatif, metode penelitian ini merupakan metode dengan cara menganalisis serta menggunakan data yang diambil pada PT. Haleyora Power, sehingga untuk mengolahnya diperlukan analisis serta perhitungan dari data yang telah didapatkan. Pada pengujian ini dimana ada lima penyulang yang digunakan sebagai sampel yaitu penyulang Scorpio, penyulang Dayung dan penyulang Libra dan penyulang Lempuyang dan penyulang Cuaca. Dengan data parameter kelembaban dan suhu, dapat dihitung tegangan pemunculan korona. Pada pengujian isolasi penyulang Scorpio didapatkan nilai tahanan isolasi yaitu 263,2 GΩ pada titik pengujian R-T, dan pada pengujian isolasi penyulang Dayung didapatkan nilai tahanan isolasi yaitu 245,2 GΩ pada titik pengujian R-S, pada pengujian isolasi penyulang Libra didapatkan nilai tahanan isolasi yaitu 242,1 GΩ pada titik pengujian S T, pada pengujian isolasi penyulang Lempuyang didapatkan nilai tahanan isolasi yaitu 124,2 MΩ pada titik pengujian S-G, pada pengujian isolasi penyulang Cuaca didapatkan nilai tahanan isolasi yaitu 242,1 MΩ pada titik pengujian R-S. Pada perhitungan untuk mendapatkan nilai tegangan kemunculan korona hal pertama yaitu mencari nilai faktor densitas dan kemudian mencari nilai tegangan kritis, Dan hal ini dapat dilihat dari pengujian tegangan tembus dengan didapatkan nilai tegangan kemunculan korona sebesar 8,95 kV sedangkan tegangan kerja dari PLN yaitu 11,56 kV.

In the distribution of electricity at substations, distribution substations, switching substations, especially the 20 kV network, disturbances often occur. The impact of the corona on a 20 kV cubicle is the occurrence of unstable voltages, power losses and insulation failures which can cause a decrease in the quality of electricity distribution to consumers. This study aims to find out what can cause the presence of corona in the cubicle, to determine the power losses caused by the corona and to find out how to overcome corona interference on the cubicle. The research method used in this study is quantitative descriptive, this research method is a method by analyzing and using data taken at PT. Haleyora Power, so that to process it, analysis and calculations are needed from the data that has been obtained. In this test, five feeders were used as samples, namely the Scorpio feeder, the Paddle feeder and the Libra feeder and the Lempuyang feeder and the Weather feeder. With the data of humidity and temperature parameters, the corona emergence voltage can be calculated. In the Scorpio feeder isolation test, the insulation resistance value was 263.2 GΩ at the R-T test point, and in the Paddle feeder isolation test, the insulation resistance value was 245.2 GΩ at the R-S test point, in the Libra feeder isolation test, the insulation resistance value was 242. .1 GΩ at the S-T test point, in the Lempuyang feeder isolation test, the insulation resistance value was 124.2 MΩ at the S-G test point, in the Weather feeder isolation test, the insulation resistance value was 242.1 MΩ at the R-S test point. In the calculation to get the voltage value of the emergence of the corona, the first thing is to look for the value of the density factor and then look for the value of the critical voltage, and this can be seen from the breakdown voltage test by getting the voltage value of the emergence of the corona of 8.95 kV while the working voltage from PLN is 11, 56 kV.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Korona, kubikel, partial discharge. Corona, cubicle, partial discharge.