HIDAYAT, RESTU AHMAD and Diantari, Retno Aita (2022) ASSESSMENT SALURAN KABEL TEGANGAN MENENGAH (SKTM) 20 KV DENGAN METODE PENGUJIAN TANGEN DELTA DAN PARTIAL DISCHARGE. Diploma thesis, ITPLN.
PROYEK AKHIR_ RESTU AHMAD H_ 201971158_RESTU AHMAD HIDAYAT.pdf
Restricted to Registered users only
Download (3MB)
Abstract
Sistem jaringan distribusi tegangan menengah (SKTM) 20 KV di perkotaan sudah sepenuhnya menggunakan sistem kabel. Jaringan distribusi dengan sistem kabel membutuhkan pemeliharaan untuk menjaga tingkat keandalan. Banyak faktor yang mempengaruhi tingkat keandalan dari sistem kabel ini salah satunya faktor lingkungan yang bisa menyebabkan deformasi pada kabel sehingga kemungkinan akan mempengaruhi kondisi dielektrik pada kabel. Oleh karenanya untuk mengetahui dan menjamin keandalan sistem kabel tersebut agar dapat diketahui andal atau tidak nya suatu kabel maka dibutuhkan suatu sistem diagnostic kondisi kabel yang dapat mengakses kondisi kabel yang ada dilapangan. Tan Delta (Disipation Factor) dan Partial Discharge (Peluahan Sebagian) merupakan pengujian yang dapat mendiagnostik kondisi isolasi kabel yang ada dilapangan. Berdasarkan pengujian tersebut maka kondisi kabel dapat ditentukan apakah dalam keadaan baik, perlu adanya perawatan secara berkala atau dalam kondisi buruk. Pada Tugas Akhir ini Assessment Kabel dilakukan pada penyulang Diskusi & Munas dengan maksud untuk mengetahui kondisi dari kabel masing-masing penyulang. Kondisi kabel pada penyulang Diskusi setelah dilakukan pengujian Tangen Delta adalah Tidak Perlu Tindakan dengan estimasi pengujian kembali setelah 5 Tahun. Untuk pengujian Partial Discharge mendapatkan point 4 yaitu status kabel Waspada dengan estimasi pengujian kembali setelah 1 Tahun. Sedangkan kondisi kabel pada penyulang Munas setelah dilakukan pengujian Tangen Delta adalah Tidak Perlu Tindakan dengan estimasi pengujian kembali setelah 5 Tahun. Untuk pengujian Partial Discharge mendapatkan point 6 yaitu status kabel Sangat Buruk dengan estimasi pengujian kembali setelah 3 Bulan. Pengujian ini mengacu pada standar yang dipakai yaitu IEEE 400.2, untuk Tangen Delta dan Standar IEEE 400.5 untuk Partial Discharge.
The 20 KV medium-voltage distribution network system (SKTM) in urban areas is fully using the cable system. Distribution network with cable system requires maintenance to maintain the level of reliability. Many factors affect the reliability of this cable system, one of which is environmental factors that can cause deformation of the cable so that it is likely to affect the dielectric condition of the cable. Therefore, to determine and ensure the reliability of the cable system so that it can be known whether a cable is reliable or not, a cable condition diagnostic system is needed that can access the existing cable conditions in the field. Tan Delta (Dissipation Factor) and Partial Discharge are tests that can diagnose the condition of cable insulation in the field. Based on these tests, the condition of the cable can be determined whether it is in good condition, needs regular maintenance or is in bad condition. In this Final Project, the Cable Assessment is carried out on the Discussion & National Conference feeders with the aim of knowing the condition of each feeder's cable. The condition of the cable in the feeder. Discussion after the Tangen Delta test is carried out, there is no need for action with an estimated re-test after 5 years. For Partial Discharge testing, it gets point 4, namely the status of the Alert cable with an estimated re-test after 1 year. While the condition of the cable at the National Conference feeder after the Tangen Delta test is No Action Needed with an estimated re-test after 5 years. For the Partial Discharge test, you get point 6, namely the status of the cable is very bad with an estimated test return after 3 months. This test refers to the standards used, namely IEEE 400.2, for Tangent Delta and IEEE Standard 400.5 for Partial Discharge.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Jaringan distribusi, SKTM 20 KV, Tan delta, Partial Discharge, Standar IEEE 400.2, Standar IEEE 400.5. Distribution network, SKTM 20 KV, Tan delta, Partial Discharge, IEEE standard 400.2, IEEE standard 400.5. |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Tenaga Listrik |
| Divisions: | Vokasi > D3 Teknologi Listrik |
| Depositing User: | Sudarman |
| Date Deposited: | 20 Apr 2026 04:50 |
| Last Modified: | 20 Apr 2026 04:50 |
| URI: | https://repository.itpln.ac.id/id/eprint/6446 |