SUGANDA, ILHAM EGI and christiono, christiono (2022) PENGUJIAN PENGARUH TEMPERATUR TERHADAP KARAKTERISTIK TEGANGAN TEMBUS ISOLASI UDARA DENGAN BENTUK DAN JARAK ANTARA DUA ELEKTRODA. Diploma thesis, ITPLN.
PROYEK AKHIR_ Ilham Egi Suganda_201971114_ILHAM EGI SUGANDA.pdf
Restricted to Registered users only
Download (1MB)
Abstract
Pada penelitian ini bertujuan mengidentifikasi pengaruh perubahan suhu terhadap nilai tegangan tembus isolasi udara. Metode pengujiannya adalah breakdown test dengan acuan standar IEC 60052 (2002). Pada pengujian diatur penurunan suhu dari 40ºC, 35ºC, 30ºC, 25ºC, 20ºC dengan menggunakan media uji elektroda jarum-jarum, batang-batang, bola-bola, dan jarum-batang dengan variasi jarak elektroda 1cm, 2cm, 3cm. Berdasarkan hasil pengujian breakdown test terdapat penurunan nilai tegangan tembus isolasi udara pada saat suhu naik terlihat pada suhu 40ºC dengan tegangan tembus 35,86 kV, sedangkan nilai tegangan tembus isolasi udara naik ketika diatur penurunan suhu pada 20ºC sebesar 42,65 kV selisih adanya penurunan suhu terhadap tegangan tembus yaitu 1,70 kV, untuk pengaruh variasi bentuk elektroda dan jarak akan mengakibatkan kenaikan nilai tegangan tembus isolasi udara terlihat pada bola-bola dengan Jarum-Jarum selisih 7,78 kV dan pengaruh jarak memiliki selisih 11,82 kV. Jadirekomendasi penggunaan isolasi udara pada suhu dingin yang baik yaitu menggunakan jarak dan elektroda lebih dari 1cm.
This study aims to identify the effect of temperature changes the value of the breakdown voltage of air insulation. test method is a breakdown test with reference to the standard IEC 60052 (2002). the test temperature drop set from 40ºC, 35ºC, 30ºC, 25ºC, 20ºC using test media for the electrodes of needles, rods, balls, with variations in the distance of the electrodes 1cm, 2cm, 3cm. Based on the results of the breakdown test, there decrease in the value of the breakdown voltage of the air insulation when the temperature rises at of 40ºC with a breakdown voltage of 35.86 kV, while the value of the breakdown voltage of the air insulation increases when the temperature drop at 20ºC is at 42,65 kV, the difference there is a decrease in temperature. the breakdown voltage 1,70 kV, the effect of variations the shape of electrode and distance will result in an increase value of the breakdown voltage the air insulation seen in the ball with a needle difference of 7,78 kV and the effect of distance has difference of 11,82 kV. So recommendation for using air insulation cold temperatures is good, namely using a distance and electrode of more than 1cm.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Tegangan Tembus, Isolasi Udara, Elektroda, Suhu, Jarak Sela. Breakdown Voltage, Air Insulation, Electrodes, Temperature, Distance. |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Tenaga Listrik |
| Divisions: | Vokasi > D3 Teknologi Listrik |
| Depositing User: | Sudarman |
| Date Deposited: | 20 Apr 2026 06:18 |
| Last Modified: | 20 Apr 2026 06:18 |
| URI: | https://repository.itpln.ac.id/id/eprint/6447 |