KOORDINASI SETTING RELAY PADA INCOMING, OUTGOING DAN CIRCUIT BREAKER OUTGOING DI PENYULANG RUBEL PT.PLN (PERSERO) UP3 PONDOK KOPI

FAUZI, MUHAMMAD RIZQI and Purwanto, Sugeng (2022) KOORDINASI SETTING RELAY PADA INCOMING, OUTGOING DAN CIRCUIT BREAKER OUTGOING DI PENYULANG RUBEL PT.PLN (PERSERO) UP3 PONDOK KOPI. Diploma thesis, ITPLN.

[thumbnail of PROYEK AKHIR MUHAMMAD RIZQI FAUZI 201971159_MUHAMMAD RIZQI FAUZI.pdf] Text
PROYEK AKHIR MUHAMMAD RIZQI FAUZI 201971159_MUHAMMAD RIZQI FAUZI.pdf
Restricted to Registered users only

Download (3MB)

Abstract

Pemasangan CBO (Circuit Breaker Outgoing) di jaringan penyulang bertujuan untuk melokalisir daerah padam. Secara umum prinsip kerjanya yaitu CBO melokalisir daerah gangguan yang berada di arah bawahnya sehingga gangguan yang terjadi tidak mengakibatkan trip di PMT penyulang. CBO dilengkapi dengan OCR dan GFR sebagai proteksi gangguan arus lebih antar fasa dan gangguan arus lebih fasa ke tanah. OCR merupakan suatu relai yang disetting untuk dapat mengatasi apabila pada penyulang rubel terindikasi adanya gangguan fasa-fasa. Sedangkan GFR merupakan relai yang digunakan untuk mengatasi apabila terindikasi adanya gangguan 1 fasa- tanah. Gangguan yang terjadi dapat mengakibatkan trip pada suatu penyulang jika tidak diatasi oleh system proteksi yang mempunyai tingkat sensitivitas yang tinggi, sehingga untuk mengatasi hal tersebut dilakukan setting relai untuk mengatasi gangguan tersebut dimana semakin dekat titik gangguan dengan relai maka semakin cepat waktu kerja relai untuk mengatasi gangguan tersebut. Pada perhitungan didapat untuk OCR dan GFR dengan TMS dan waktu pada sisi incoming penyulang 0,28 tms dengan waktu 0,98 detik, GFR 0,23 tms dengan waktu 1,04 detik, sisi outgoing penyulang untuk OCR 0,37 tms dengan waktu 0,69 detik, GFR 0,25 tms dengan waktu 0,69 detik, dan untuk CBO penyulang dimana OCR 0,12 tms dengan waktu 0,20 detik, GFR 0,10 tms dengan waktu 0,28 detik. Berdasarkan hasil perhitungan setting relai yang dilakukan penulis maka terbukti bahwa waktu kerja relai pada CBO penyulang lebih cepat dibandingkan dengan relai pada sisi outgoing dan incoming penyulang.

Installation of CBO (Circuit Breaker Outgoing) in the feeder network aims to localize outages. In general, the working principle is that the CBO localizes the fault area that is below it so that the disturbance that occurs does not result in a trip at the feeder PMT. CBO is equipped with OCR and GFR as an inter-phase overcurrent fault protection and phase to ground overcurrent fault. OCR is a relay that is set to be able to overcome if the ruble feeder indicates a phase fault. While the GFR is a relay that is used to overcome if there is an indication of a single phase-ground fault. The disturbance that occurs can result in a trip to a feeder if it is not overcome by a protection system that has a high level of sensitivity, so to overcome this, a relay setting is carried out to overcome the disturbance where the closer the fault point to the relay is, the faster the relay working time to overcome the disturbance. the. In the calculation obtained for OCR and GFR with TMS and time on the incoming feeder 0.28 tms with a time of 0.98 seconds, GFR 0.23 tms with a time of 1.04 seconds, the outgoing side of the feeder for OCR 0.37 tms with a time of 0 .69 seconds, GFR 0.25 tms with a time of 0.69 seconds, and for CBO feeders where OCR 0.12 tms with a time of 0.20 seconds, GFR 0.10 tms with a time of 0.28 seconds. Based on the calculation of the relay settings made by the author, it is proven that the relay working time on the feeder CBO is faster than the relay on the outgoing and incoming feeder.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Proteksi CBO (Circuit Breaker Outgoing), OCR, GFR, Gangguan. Protection CBO (Circuit Breaker Outgoing), OCR, GFR, Blackout.
Subjects: Skripsi
Bidang Keilmuan > Teknik Tenaga Listrik
Divisions: Vokasi > D3 Teknologi Listrik
Depositing User: Sudarman
Date Deposited: 20 Apr 2026 07:19
Last Modified: 20 Apr 2026 07:19
URI: https://repository.itpln.ac.id/id/eprint/6450