Abstract
Transformator distribusi di PT. PLN (Persero) UP3 Banda Aceh ULP Merduati yaitu tepatnya trafo distribusi pada penyulang lamteumen terjadi transformator yang mengalami keadaan overload dengan persentase pembebanan sebesar 100% yang dimana hal tersebut melebihi standar yang sudah ditetapkan SPLN yaitu sebesar 80%. Tujuan dari penulisan ini dibuat untuk mengetahui cara menanggulangi masalah transformator yang mengalami keadaan overload pada gardu distribusi Penyulang Lamteumen serta menganalisis hasil persentase besar pembebanan di transformator sebelum dan sesudah Relokasi transformator. Peneliti membuat penulisan tugas akhir ini dengan cara kualitatif yaitu mengumpulkan data-data yang ada di UP3 Banda Aceh ULP Merduati, serta melakukan sesi tanya jawab dengan pembimbing lapangan kemudian melakukan studi literatur yang mendukung penyelesaian masalah pada transformator yang overload. Oleh karena itu dalam mengatasi masalah transformator yang overload pada trafo penyulang lamteumen dilakukan perbaikan dengan melihat kondisi tersebut salah satunya dengan melakukan relokasi transformator dengan kapasitas yang lebih besar menjadi 160 kVA sampai 200 kVA dari sebelumnya yaitu 100 kVA. Dari hasil dilakukan nya relokasi diperoleh hasil nilai persentase pembebanan trafo sebesar 72,2535% yang dimana sebelum dilakukan relokasi trafo yaitu 144,507%, sehingga mengalami penurunan sebanyak 72,2%. kemudian trafo selanjutnya dilakukan nya relokasi diperoleh hasil nilai persentase pembebanan trafo sebesar 71,30625% yang dimana sebelum dilakukan relokasi trafo yaitu 114,09% sehingga mengalami penurunan sebanyak 42,78375 % dan pada trafo ke tiga relokasi diperoleh hasil nilai persentase pembebanan trafo sebesar 56,469 % yang dimana sebelum dilakukan relokasi trafo yaitu 112,938 %, sehingga mengalami penurunan sebanyak 56,469 %.Kemudian dapat dilihat dari persentase pembeban di atas kapasitas 160 dan 200 kVA pemakaian beban semakin berkurang. Hal ini membuktikan bahwa relokasi transformator merupakan salah satu metode yang bisa digunakan untuk mengatasi masalah overload pada gardu distribusi.
Distribution transformer at PT. PLN (Persero) UP3 Banda Aceh ULP Merduati, that is the distribution transformer at the lamteumen feeder, the transformer is experiencing an overload state with a loading percentage of 100% which exceeds the standard set by SPLN, which is 80%. The purpose of this paper is to find out how to overcome the problem of transformers experiencing overload conditions at the Lamteumen Feeder distribution substation and to analyze the results of the large percentage of loading on the transformer before and after transformer relocation. The researcher wrote this final project in a qualitative way, namely collecting data in UP3 Banda Aceh ULP Merduati, and conducting a question and answer session with the field supervisor and then conducting a literature study that supports solving the problem of overloaded transformers. Therefore, in overcoming the problem of an overloaded transformer on the lamteumen feeder transformer, improvements were made by looking at these conditions, one of which was by relocating a transformer with a larger capacity to 160 kVA to 200 kVA from the previous 100 kVA. From the results of the relocation, the percentage value of the transformer loading is 72.2535% which before the transformer relocation was 144.507%, so it decreased by 72.2%. then the next transformer is relocated, the result is that the percentage value of the transformer loading is 71.30625%, which before the transformer relocation was 114.09% so that it decreased by 42.78375% and in the third relocation transformer the percentage value of the transformer loading was 56.469 % which before the relocation of the transformer was 112,938%, so it decreased by 56,469%. Then it can be seen from the percentage of loading above the capacity of 160 and 200 kVA the use of the load is decreasing. This proves that transformer relocation is one method that can be used to overcome the problem of overload at distribution substations.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Transformer, loading, overload, power Transformmator , pembebanan ,overload,daya |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Tenaga Listrik |
| Divisions: | Vokasi > D3 Teknologi Listrik |
| Depositing User: | Sudarman |
| Date Deposited: | 21 Apr 2026 04:48 |
| Last Modified: | 21 Apr 2026 04:48 |
| URI: | https://repository.itpln.ac.id/id/eprint/6455 |