HUZAIRI, MOCHAMMAD AQMAL and Purwanto, Sugeng (2022) ANALISA PERHITUNGAN KEBUTUHAN KAPASITAS BACK-UP GENSET MITSUBISHI 2 x 1600 KVA PADA APARTEMEN THE STATURE JAKARTA. Diploma thesis, ITPLN.
55. PROYEKAKHIR(pdf)_M.AQMALHUZAIRI_201971015.pdf
Restricted to Registered users only
Download (2MB)
Abstract
Apartemen The Stature Jakarta adalah apartemen yang memiliki 30 lantai dengan masing – masing tipe unit mulai dari tipe unit A, B, C, D, E, F, G, H, dan unit I. Penelitian dilakukan untuk membandingkan hasil perhitungan kapasitas genset dengan aktualisasi genset yang sudah terpasang pada apartemen The stature jakarta dengan mengguanakn metode penelitian kuantitatif yaitu dengan mengolah data numerik untuk dianalisa dan diambil kesimpulannya. Berdasarkan hasil perhitungan yang dilakukan, didapatkan hasil bahwa besar kapasitas daya genset yang diperlukan sebagai cadangan energi listrik adalah sebesar 1821,47 KVA/1457,176 kW. Sedangkan kapasitas genset adalah 2560 kVA/2048 kW, maka kapasitas daya genset yang ada sudah memenuhi kebutuhan beban gedung apartemen tersebut. Nilai efisiensi genset saat pembebanan 1003 kW adalah sebesar 48 % yang disebabkan pembebanan hanya 16 % dari total beban yang terpasang. Rating pengaman ACB yang ditemukan adalah 2332,8 A, namun untuk menjamin keamanan, rating pengaman harus lebih tinggi dari itu, maka ACB yang dipasang adalah dengan rating 2500 A. Kemudian, konsumsi bahan bakar genset saat dibebankan sebesar 325 kW adalah memerlukan bahan bakar solar sebanyak 85,32 liter/jam. Dari perbandingan dengan aktualisasi dilapangan, maka dapat dikatakan pemasangan genset kapasitas 1600 kVA sudah memenuhi kebutuhan daya darurat apartemen The Stature Jakarta.
The Stature Jakarta Apartment is an apartment that has 30 floors with each type of unit starting from unit types A, B, C, D, E, F, G, H, and unit I. Research was conducted to compare the results of the calculation of generator capacity with the actualization of the generator set that has been installed in The stature jakarta apartment by using quantitative research methods, namely by processing numerical data for analysis and conclusions. Based on the results of the calculations carried out, it was found that the amount of generator power capacity needed as a backup of electrical energy was 1821.47 KVA / 1457.176 kW. While the generator capacity is 2560 kVA / 2048 kW, the existing generator power capacity already meets the load needs of the apartment building. The efficiency value of the generator set when loading 1003 kW is 48% which is due to the loading of only 16% of the total installed load. The ACB safety rating found is 2332.8 A, but to ensure safety, the safety rating must be higher than that, then the ACB installed is with a rating of 2500 A. Then, the fuel consumption of the generator when charged at 325 kW is that it requires 85.32 liters of diesel fuel / hour. From the comparison with the actualization in the field, it can be said that the installation of a generator with a capacity of 1600 kVA has met the emergency power needs of The Stature Jakarta apartment.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | genset, kapasitas daya, rating pengaman generator set, power capacity, safety rating |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Tenaga Listrik |
| Divisions: | Vokasi > D3 Teknologi Listrik |
| Depositing User: | Sudarman |
| Date Deposited: | 21 Apr 2026 05:08 |
| Last Modified: | 21 Apr 2026 05:08 |
| URI: | https://repository.itpln.ac.id/id/eprint/6458 |