TOBING, WILLY PRANATA L and Pasra, Nurmiati (2022) PENGARUH KORONA TERHADAP RUGI-RUGI DAYA DAN ENERGI TAK TERJUAL PADA KUBIKEL PENYULANG 20 KV DI GIS DANAYASA DAN GIS TAMARA. Diploma thesis, ITPLN.
PROYEK AKHIR_WILLY PRANATA L TOBING_201971128_WILLY PRANATA L TOBI.pdf
Restricted to Registered users only
Download (2MB)
Abstract
Pada sistem distribusi tenaga listrik sering terjadi gangguan yaitu korona pada kubikel yang mampu menurunkan keandalan sistem penyaluran energi listrik. Korona terjadi karena adanya pengaruh suhu dan kelembaban yang menyebabkan udara di sekitar penghantar terkena korona. Gangguan korona ini dapat menyebabkan rugi-rugi daya dan energi tak terjual, dimana ada tiga penyulang yang digunakan sebagai sempel yaitu penyulang Portugal, penyulang Bidakara dan penyulang Email. Dengan data parameter kelembapan dan suhu, dapat di hitung tegangan pemunculan korona yang/ tegangan distruptif kritis, saat tegangan distruptif semakin kecil maka rugi-rugi daya yang ditimbulkan akan semakin besar. Dari ketiga penyulang yang menjadi objek penelitian didapat hasil rugi-rugi daya pada penyulang Portugal 94,6008 kW, Penyulang Bidakara 94,0086 kW dan Penyulang Email sebesar 88,8313 kW dan nilai energi tak terjual pada penyulang Portugal sebesar 2270,42 kWh dengan rupiah sebesar Rp. 3.280.075,774, Penyulang Bidakara sebesar 2160,20 kWh dengan rupiah sebesar Rp.3.120.840,94 dan penyulang Email sebesar 2131,95 dengan rupiah sebesar Rp.3.080.028,16. Korona dapat ditangani dengan melakukan pemeliharaan, dengan membersihkan bagian yang terkena menggunakan cairan sekapen cleaning paste dan kertas pasir, mengilangkan bagian yang runcing menggunkan kertas pasir dan membersihkan bagian kubikel dari pertikel debu dengan kain majun. Rugi-rugi daya yang diakibatkan oleh korona berbanding lurus dengan energi tak terjual.
In the electric power distribution system, disturbances often occur, namely the corona in the cubicle which can reduce the reliability of the electrical energy distribution system. Corona occurs due to the influence of temperature and humidity which causes the air around the conductor to be exposed to corona. This corona disturbance can cause unsold power and energy losses, where there are three feeders used as samples, namely the Portugal feeder, the Bidakara feeder and the Email feeder. With the data of humidity and temperature parameters, it can be calculated the corona emergence voltage/critical disruptive voltage, when the disruptive voltage gets smaller, the power losses generated will be even greater. From the three feeders that became the object of the study, the results of the power losses on the Portugal feeder were 94,6008 kW, the Bidakara feeder 94,0086 kW and the Email feeder of 88,8313 kW and the value of unsold energy for the Portuguese feeder was 2270,42 kWh in rupiah. of Rp. 3,280,075,774, Bidakara feeder of 2160.20 kWh with rupiah of Rp.3,120,840.94 and Email feeder of 2131.95 with rupiah of Rp.3,080,028.16. Corona can be treated by carrying out maintenance, by cleaning the affected area using a cleaning paste and sand paper, removing the sharp parts using sand paper and cleaning the cubicle of dust particles with a cloth. The power losses caused by the corona are directly proportional to the unsold energy.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | korona, rugi-rugi daya, energi tak terjual corona, power losses, energy not sale |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Tenaga Listrik |
| Divisions: | Vokasi > D3 Teknologi Listrik |
| Depositing User: | Sudarman |
| Date Deposited: | 22 Apr 2026 07:24 |
| Last Modified: | 22 Apr 2026 07:24 |
| URI: | https://repository.itpln.ac.id/id/eprint/6482 |