Abstract
pada segmen PNA 9K-GI Tangerang terdapat indikasi gangguan berulang, maka dilakukan Assessment SKTM kembali untuk mengetahui kehandalan penyulang dengan metode very low frequency. Dikatakan kondisi baik jika tidak terjadi tembus tegangan (breakdown voltage) dan memenuhi standar IEEE Std 400.2-2004 tabel 5 mengenai standar nilai tegangan tembus. Terdapat 3 parameter yang menentukan kabel dalam kondisi baik atau buruk yaitu isolasi kabel dengan standar 1000 x tegangan kerja yaitu 20 MΩ, arus bocor maksimum yang diijinkan adalah 1mA dan tegangan tembus dengan isolasi kabel XLPE dengan standar dapat menahan tegangan tembus pada tegangan >30 kV. Diperoleh hasilnya pada segmen PNA 9K GI Tangerang, tegangan yang diinject 45 kV dengan nilai isolasi fasa R,S,T berurut 1 MΩ, 2,8 MΩ, 3,1 MΩ. Nilai arus bocor 23 mA, 11,8 mA dan17,7 mA. Untuk tegangan tembus saat 1 kV, 2,8 kV dan 3,1 kV. Hasil dari ketiga fasa untuk ketiga parameter tidak memenuhi standar. Maka dinyatakan bahwa segmen kabel PNA 9K-GI Tangerang terjadi kegagalan isolasi yang menyebabkan tembus tegangan (breakdown voltage). Terjadinya tegangan tembus (breakdown voltage) dapat menyebabkan trip penyulang yang merugikan dari sisi penjualan kWh. Sehingga dilakukan tindakan lanjut yaitu deteksi kabel agar dapat dinormalkan kembali. Dari data yang diperoleh terjadi penurunan jumlah gangguan sebesar 13% di semester 1 tahun 2020-2022 yang menguntungkan penjualan energi dan peningkatan kehandalan listrik di sisi PLN
Based on the segment parameters of UP3 Cikokol where in terms of the number of times the disturbances that have occurred in the Tangerang 9K-GI PNA segment there are indications of repeated disturbances, the SKTM Assessment is carried out again to determine the reliability of the feeder with the very low frequency method. It is said to be in good condition if there is no breakdown voltage and it meets the IEEE Std 400.2-2004 table 5 standard regarding the breakdown voltage value standard. There are 3 parameters that determine whether the cable is in good or bad condition, namely cable insulation with a standard 1000 x working voltage, which is 20 MΩ, the maximum allowable leakage current is 1mA and the breakdown voltage with standard XLPE cable insulation can withstand a breakdown voltage of >30 kV. The results obtained in the Tangerang 9K-GI PNA segment, the injected voltage is 45 kV with the R,S,T phase isolation values in the order of 1MΩ, 2.8 MΩ, 3,1 MΩ. The rated leakage current is 23mA, 11.8mA and 17.7mA. For breakdown voltages when 1 kV, 2.8 kV and 3.1 kV. The results of the three phases for the three parameters do not meet the standards. Then it is stated that the Tangerang 9K-GI PNA cable segment has an insulation failure that causes breakdown voltage. The occurrence of breakdown voltage (breakdown voltage) can cause an adverse feeder trip in terms of kWh sales. So that further action is taken, namely cable detection so that it can be normalized again. From the data obtained, there was a decrease in the number of disturbances by 13% in semester 1 of 2020-2022 which benefited energy sales and increased reliability of electricity on the side of PLN.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Assessment SKTM, Very Low Frequency (VLF), Breakdown Voltage, Tahanan Isolasi Assessment SKTM, Very Low Frequency (VLF), Breakdown Voltage, Insulation Resistance |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Tenaga Listrik |
| Divisions: | Vokasi > D3 Teknologi Listrik |
| Depositing User: | Sudarman |
| Date Deposited: | 22 Apr 2026 07:52 |
| Last Modified: | 22 Apr 2026 07:52 |
| URI: | https://repository.itpln.ac.id/id/eprint/6487 |