FADHILAH, ROSSY RAHMA and Azzahra, Septianissa (2022) OPTIMASI PEMAKAIAN GROUND FAULT DETECTOR (GFD) PADA JARINGAN SPINDLE SALURAN KABEL TEGANGAN MENENGAH (SKTM) 20 KV DI PT. PLN (PERSERO) UNIT PELAKSANA PELAYANAN PELANGGAN (UP3) PONDOK KOPI. Diploma thesis, ITPLN.
PROYEK AKHIR_ROSSY RAHMA FADHILAH_201971156_ROSSY RAHMA FADHILAH.pdf
Restricted to Registered users only
Download (2MB)
Abstract
Sistem Distribusi Tenaga Listrik pada dasarnya adalah suatu proses penyaluran sistem tenaga listrik dari Transmisi 150 kV sampai ke konsumen 20 kV ataupun konsumen 380/220 Volt. Suatu sistem tenaga listrik, khususnya sistem pendistribusian yang dikatakan andal dapat dilihat dari operasi sistem tenaga listrik yang jarang terjadi pemadaman listrik di kalangan konsumen. Tetapi, kenyataannya bahwa kebanyakan sistem distribusi masih sering terjadi gangguan, baik gangguan hubung singkat maupun gangguan lainnya yang seringkali ditemukan di bagian jaringan spindel SKTM 20 Kv. Ketika ada gangguan, masih seringkali lokasi gangguan tersebut tidak langsung terdeteksi dan mengakibatkan terjadinya pemadaman listrik yang cukup lama karena menghabiskan waktu yang lama untuk mengetahui dimana letak dari gangguan tersebut dan banyak menghabiskan waktu yang cukup lama untuk penyalaan listriknya kembali. Solusi dari permasalahan tersebut yaitu dilakukanlah pemasangan suatu alat yang disebut dengan GFD. GFD (Ground Fault Detector) adalah : Suatu alat yang digunakan untuk mendeteksi adanya gangguan hubung singkat Antara fasa ke tanah pada SKTM 20 kV. Pada penelitian yang sudah dilakukan, dapat dilihat perbandingan antara total lama padam sebelum dipasang GFD jauh lebih besar yaitu 427 menit jika dibandingkan dengan total lama padam setelah dipasang GFD sebesar 224 menit. Untuk total kWh yang tidak terjual sebelum dipasang GFD bisa mencapai 23.504,36 kWh Sedangkan. Sedangkan untuk kWh yang tidak terjual sesudah dipasang GFD akan menurun menjadi 11.601,273 kWh. Dan untuk total rupiah tidak terjual sebelum pemasangan GFD yang diperoleh berkisar Rp 33.956.748,892 dan total rupiah yang tidak terjual sesudah pemasangan GFD menurun menjadi Rp 16.760.359,103.
The Electric Power Distribution System is basically a process of distributing the electric power system from 150 kV transmission to 20 kV consumers or 380/220 Volt consumers. An electric power system, especially a distribution system that is said to be reliable, can be seen from the operation of the electric power system, which rarely occurs power outages among consumers. However, we can see for ourselves that most distribution systems still frequently experience disturbances, both short circuit faults and other disturbances that are often found in the 20 Kv SKTM spindle network. When there is a disturbance, it is still often the location of the disturbance that is not immediately detected and results in a long power outage because it takes a long time to find out where the disturbance is and spends a lot of time getting the electricity back on. The solution to this problem is to install a tool called a GFD. GFD (Ground Fault Detector) is: A tool used to detect the presence of short circuit faults between phase to ground on SKTM 20 kV. In the research that has been done, it can be seen that the comparison between the total length of outage before the GFD is installed is much greater, namely 427 minutes when compared to the total length of outage after the GFD is installed of 224 minutes. The total unsold kWh before the GFD was installed could reach 23.504,36 kWh. Meanwhile, the unsold kWh after the GFD is installed will decrease to 11.601,273 kWh.. And for the total unsold rupiahs before the installation of GFD obtained around Rp 33.956.748,892 and the total unsold rupiahs after the installation of GFD decreased to Rp 16.760.359,103
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Penyusutan, Gangguan SKTM, Ground Fault Detector (GFD) Shrinkage, SKTM Disturbance, Ground Fault Detector (GFD) |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Tenaga Listrik |
| Divisions: | Vokasi > D3 Teknologi Listrik |
| Depositing User: | Sudarman |
| Date Deposited: | 23 Apr 2026 01:50 |
| Last Modified: | 23 Apr 2026 01:50 |
| URI: | https://repository.itpln.ac.id/id/eprint/6497 |