EVALUASI PENGGANTIAN KWH METER 3 FASA YANG TERPASANG PADA PELANGGAN TERHADAP HASIL PENGUKURAN ENERGI LISTRIK DI PT PLN (PERSERO) ULP RAJAPOLAH TASIKMALAYA

ALAMSYAH, RACHMAT PUJA and Sukmajati, Sigit (2022) EVALUASI PENGGANTIAN KWH METER 3 FASA YANG TERPASANG PADA PELANGGAN TERHADAP HASIL PENGUKURAN ENERGI LISTRIK DI PT PLN (PERSERO) ULP RAJAPOLAH TASIKMALAYA. Diploma thesis, ITPLN.

[thumbnail of PROYEK AKHIR_RACHMAT PUJA ALAMSYAH_201971002_RACHMAT PUJA ALAMSYA.pdf] Text
PROYEK AKHIR_RACHMAT PUJA ALAMSYAH_201971002_RACHMAT PUJA ALAMSYA.pdf
Restricted to Registered users only

Download (3MB)

Abstract

Penggantian Kilo Watt Hour Meter (KWH meter) analog ini pada saat dilakukannya pengukuran kWh lama pada pelanggan didapatkan persentase yang melebihi yang telah ditetapkan oleh oleh PT PLN (Persero). Pada PT. PLN ULP Rajapolah masih terpasang kWh meter tipe Actaris tahun buatan 2009, 2010 yang sering dilaporkan terdapat anomali pada pengukuran energi listrik yang menyebabkan tidak sesuainya pengukuran energi listrik pada pelanggan. Maka sebab itu dilakukan pemeriksaan pada nilai error kWh meter bertipe actaris serta dilakukan penggantian kWh meter jika nilai error nya melebihi batas kesalahan sebesar >10% dan menghitung penambahan tagihan pemakaian listrik pelanggan yang di sebabkan error kWh meternya. Didapatkan hasil nilai error kWh meter yakni 46,5%, 23,9%, 26,3%, 15,7% dan 32,9% dan Didapatkan nilai error sesudah melakukan pergantian kWh meter 0,657%, 0,96%, 0,56%, 0,2% dan 0,45% yang mendapat kan hasil nilai error kembali normal tidak melebihi >10%. Setelah dilakukan penggantian kWh meter terhitung hasil penambahan tagihan pada pelanggan yang nilai error nya melebihi batas sebesar Rp. 3.128.557,88.

This analogue Kilo Watt Hour Meter (KWH meter) replacement when measuring the old kWh on the customer is obtained a percentage that exceeds what has been set by PT PLN (Persero). At PT. PLN ULP Rajapolah is still installed with Actaris type KWh meter made in 2009, 2010 which is often reported as having an anomaly in the measurement of electrical energy which causes the measurement of electrical energy to be inappropriate for customers. Therefore, an examination of the error value of the actaris type kWh meter is carried out and a kWh meter replacement is carried out if the error value exceeds the error limit of >10% and calculates the addition of the customer's electricity usage bill caused by the kWh meter error. The results of the error values of the KWh meter are 46.5%, 23.9%, 26.3%, 15.7% and 32.9% and the error values obtained after changing the kWh meter are 0.657%, 0.96%, 0.56% , 0.2% and 0.45% which got the error value back to normal not exceeding >10%. After replacing the kWh meter, the results of adding bills to customers whose error value exceeds the limit of Rp. 3.128.557,88.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: kWh Meter, Error kWh, Actaris kWh Meters, Error kWh, Actaris
Subjects: Skripsi
Bidang Keilmuan > Teknik Tenaga Listrik
Divisions: Vokasi > D3 Teknologi Listrik
Depositing User: Sudarman
Date Deposited: 23 Apr 2026 02:26
Last Modified: 23 Apr 2026 02:26
URI: https://repository.itpln.ac.id/id/eprint/6506

Actions (login required)