KAJIAN HASIL COMMISSIONING PMT MEDIA SF6 PADA BAY GOMBONG DI GARDU INDUK 150 KV RAWALO UPT PURWOKERTO

NURMALASARI, PUPUT and Pahiyanti, Novi Gusti (2022) KAJIAN HASIL COMMISSIONING PMT MEDIA SF6 PADA BAY GOMBONG DI GARDU INDUK 150 KV RAWALO UPT PURWOKERTO. Diploma thesis, ITPLN.

[thumbnail of PROYEK AKHIR_PUPUT NURMALASARI_201971020_PUPUT NURMALASARI.pdf] Text
PROYEK AKHIR_PUPUT NURMALASARI_201971020_PUPUT NURMALASARI.pdf
Restricted to Registered users only

Download (4MB)

Abstract

Pemeliharaan merupakan upaya terpenting uyang dpaat dilakukan untuk menjaga peralatan – peralatan listrik dapat bekerja secara optimal dan juga menjaga life time peralatan. Salah satu pemeliharan yang dilakukan di Gardu Induk 150 kV Rawalo yaitu dengan melakukan pemeliharaan Pemutus Tenaga (PMT), dimana PMT ini berfungsi sebagai saklar pengaman, pemutus dan menutup arus beban baik dalam kondisi normal maupun abnormal. PMT incoming bay gombong merupakan PMT yang sistem penggeraknya menggunakan system hidrolik dan sudah digunakan dari tahun 1993 dimana kondisi terkini PMT tersebut mengalami rembes minyak. Oleh karena itu, dilakukanlah penggantian PMT dengan sistem penggerak pegas. Untuk memastikan PMT baru dapat bekerja dilakukan commissioning dengan cara pengujian tahanan isolasi, tahanan kontak, keserempakan PMT, kemurnian gas SF6 dan tahanan pentanahan menggunakan peralatan seperti insulation tester, Mjolner 600, breaker analyzer, SF6 Q Analyzer dan digital earth tester. Dari hasil uji didapatkan semua konsisi pengujian sesuai dengan standar PLN. Dari hasil uji ini maka dapat disimpulkan PMT dapat dioperasikan. Dapat diperoleh hasil pengujian tahanan isolasi pada PMT baru yang lebih baik yaitu nilainya di atas 1kV/1MΩ. Pada hasil pengujian tahanan kontak juga diperoleh hasil dibawah 50µΩ. Begitupun pada pengujian keserempakan delta time yang didapat < 10 ms. Pada pengujian kemurnian gas SF6 diperoleh tekanan gasnya diatas 5 bar. Pengujian tahanan pentanahan <1Ω.

Maintenance is the most important effort that can be done to keep electrical equipment working optimally and also to maintain equipment life time. One of the maintenance carried out at the Rawalo 150 kV Substation is by performing power breaker maintenance (PMT), where this PMT functions as a safety switch, breaker and closes the load current in both normal and abnormal conditions. PMT incoming bay gombong is a PMT whose drive system uses a hydraulic system and has been in use since 1993 where the current condition of the PMT is experiencing oil seepage. Therefore, the PMT was replaced with a spring drive system. To ensure the new PMT can work, commissioning is carried out by testing insulation resistance, contact resistance, PMT simultaneous, SF6 gas purity and grounding resistance using equipment such as insulation tester, Mjolner 600, breaker analyzer, SF6 Q-Analyzer and digital earth tester. From the test results, all test conditions are in accordance with PLN standards. From the results of this test, it can be concluded that PMT can be operated. The results of the insulation resistance test on the new PMT are better, namely the value is above 1kV/1MΩ. The results of the contact resistance test also obtained results below 50µΩ. Likewise in the delta time synchronous test obtained < 10 ms. In testing the purity of SF6 gas, the gas pressure was obtained above 5 bar. Ground resistance test < 1Ω

Item Type: Thesis (Diploma)
Uncontrolled Keywords: PMT, Tahanan Isolasi, Tahanan Kontak, Keserempakan, Kemurnian gas SF6, Tahanan Pentanahan PMT, Isolation Resistance, Contact Resistance, Simultaneous, SF6 gas purity, Grounding Resistance
Subjects: Skripsi
Bidang Keilmuan > Teknik Tenaga Listrik
Divisions: Vokasi > D3 Teknologi Listrik
Depositing User: Sudarman
Date Deposited: 23 Apr 2026 02:37
Last Modified: 23 Apr 2026 02:37
URI: https://repository.itpln.ac.id/id/eprint/6508