ANALISIS PERBANDINGAN HASIL PENGUJIAN TAHANAN ISOLASI, TAHANAN KONTAK DAN KEBOCORAN ARUS DENGAN HASIL PERHITUNGAN PADA DULFUR PENYULANG GADUNG GARDU INDUK CAWANG BARU

SURI, MUTIARA PRASTUSIA PASHA and Hutajulu, Albert Gifson (2022) ANALISIS PERBANDINGAN HASIL PENGUJIAN TAHANAN ISOLASI, TAHANAN KONTAK DAN KEBOCORAN ARUS DENGAN HASIL PERHITUNGAN PADA DULFUR PENYULANG GADUNG GARDU INDUK CAWANG BARU. Diploma thesis, ITPLN.

[thumbnail of PROYEK AKHIR_MUTIARA PRASTUSIA PASHA SURI_201_MUTIARA PRASTUSIA PA.pdf] Text
PROYEK AKHIR_MUTIARA PRASTUSIA PASHA SURI_201_MUTIARA PRASTUSIA PA.pdf
Restricted to Registered users only

Download (4MB)

Abstract

Pada gardu induk Cawang Baru terdapat gangguan dulfur penyulang Gadung maka dilakukan pengujian tahanan isolasi, tahanan kontak dan kebocoran arus. Tujuan dilakukan penelitian berguna untuk mengetahui perbandingan hasil pengujian tahanan isolasi, tahanan kontak dan kebocoran arus dulfur, untuk mengetahui hasil pengujian sesuai dengan standar dan untuk melakukan perawatan yang dilakukan apabila menghasilkan nilai yang tidak sesuai standar yang digunakan. Metode analisa data yang digunakan dengan cara melakukan perbandingan perhitungan dengan hasil pengujian sesuai dengan standar yang digunakan PLN atau tidak. Hasil pengujian tahanan isolasi sesuai standar pengujian dulfur gadung setelah pembersihan fasa R hasilnya 164 MΩ, fasa S hasilnya 119 MΩ, dan fasa T hasilnya 170 MΩ. Pengujian dulfur LRT setelah penggantian isolator dengan hasil fasa R hasilnya 9,5 GΩ, fasa S hasilnya 2,68 GΩ, dan fasa T hasilnya 5,27 GΩ. Hasil pengujian tahanan isolasi yang tidak sesuai standar pada pengujian dulfur sebelum pembersihan fasa S dan T menghasilkan nilai 0. Pengujian tahanan kontak menghasilkan nilai tidak sesuai standar pengujian busbar B fasa R hasilnya 168 µ, fasa S hasilnya 188 µ, dan fasa T hasilnya 186 µ. Pengujian kebocoran arus hasilnya memenuhi standar, pengujian busbar B pada fasa R, S dan T dengan nilai 0,03 mA.

At the Cawang Baru substation, there is a disturbance in the Gadung feeder dulfur, so testing for insulation resistance, contact resistance and leakage current is carried out. The purpose of this research is to find out the comparison of the results of the insulation resistance test, contact resistance and leakage current dulfur, to find out the test results are in accordance with the standards and to carry out maintenance if they produce values that do not match the standards used. The data analysis method used is by comparing the calculations with the test results in accordance with the standards used by PLN or not. The results of the insulation resistance test according to the dulfur gadung test standard after cleaning the R phase the result is 164 MΩ, the S phase is 119 MΩ, and the T phase is 170 MΩ. The dulfur LRT test after replacing the insulator with the results of the R phase was 9.5 GΩ, the S phase was 2.68 GΩ, and the T phase was 5.27 GΩ. The results of the insulation resistance test that do not meet the standards in the dulfur test before cleaning the S and T phases produce a value of 0. The contact resistance test results in a value that does not meet the standard for the busbar test, B phase R, the result is 168 µΩ, the S phase is 188 µΩ, and the T phase is the result. 186 µΩ. The current leakage test results meet the standard, busbar B testing in the R, S and T phases with a value of 0.03 mA.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: tahanan isolasi, tahanan kontak, kebocoran arus, standar insulation resistance, contact resistance, leakage current, standard
Subjects: Skripsi
Bidang Keilmuan > Teknik Tenaga Listrik
Divisions: Vokasi > D3 Teknologi Listrik
Depositing User: Sudarman
Date Deposited: 23 Apr 2026 05:21
Last Modified: 23 Apr 2026 05:21
URI: https://repository.itpln.ac.id/id/eprint/6518