PENGARUH CORECTIVE MAINTENANCE TERHADAP PENURUNAN SUHU GT CCW COOLER FAN PADA UNIT 1 UJP PLTGU CILEGON

Prawira, Galih Wildhan and Sulistiyo, Eko (2019) PENGARUH CORECTIVE MAINTENANCE TERHADAP PENURUNAN SUHU GT CCW COOLER FAN PADA UNIT 1 UJP PLTGU CILEGON. Diploma thesis, ITPLN.

[thumbnail of PROYEK AKHIR GALIH WILDHAN PRAWIRA 201572015.pdf] Text
PROYEK AKHIR GALIH WILDHAN PRAWIRA 201572015.pdf
Restricted to Registered users only

Download (1MB)

Abstract

GT CCW Cooler Fan (Gas Turbine Close Cooling Water Cooler Fan) merupakan alat penukar kalor dimana berfungsi untuk mendinginkan air CCW yang telah digunakan untuk mendinginkan komponen Auxiliary Gas Turbine. CCW sendiri memanfaatkan air demin sebagai fluida untuk mendinginkan komponen Auxiliary Gas Turbine itu sendiri dan dijaga konduktivitas airnya agar tetap konstan. Dikarenakan penggunaan GT CCW Cooler Fan terus menerus maka dilakukannya pemeliharaan agar komponen ini tidak rusak dan bertahan lama. Pemeliharaan yang dilakukan pada komponen GT CCW Cooler Fan harus dilakukan dengan cara yang tepat agar kinerja dari GT CCW Cooler Fan itu sendiri tetap terjaga kualitasnya. Setelah diperoleh data penelitian yang dibutuhkan yang didapat dari data primer maupun skunder, data tersebut dihitung efektivitas termal dengan menggunakan metode LMTD (Log Mean Temperature Difference) yaitu rata-rata logaritmik dari perbedaan suhu antara fluida yang akan didinginkan dan fluida yang mendinginkan. Dari hasil perhitungan sebelum dilakukan perbaikan diperoleh hasil nilai LMTD sebesar 2,325 °C, 2,814 °C, 2,926 °C, 2,029 °C, 2,741 °C sebelum perbaikan dan didapat 2,245 °C, 1,529 °C, 2,231 °C, 1,529 °C, 1,581 °C setelah dilakukan perbaikan. Jika nilai LMTD naik, maka panas yang dibebaskan akan berkurang. Sedangkan jika nilai LMTD turun, maka panas yang akan dibebaskan akan semakin besar. Setelah dilakukan perbaikan pada GT CCW Cooler Fan terjadi penurunan temperature pada Closed Cooling Water sehingga air yang digunakan untuk mendinginkan Auxiliary Gas Turbine juga akan mengalami penurunan.

The GT CCW Cooler Fan is a heat exchanger used to cool CCW air that has been used to cool the Auxiliary Gas Turbine components. CCW itself uses water as a fluid to cool the component of the Auxiliary Gas Turbine itself and the water conductivity is kept constant. Due to the continuous use of the GT CCW Cooler Fan, maintenance is needed so that these components are not damaged and last a long time. Maintenance carried out on Cooler Fan GT CCW components must be done in an appropriate manner so that the performance of the Cooler Fan GT CCW must maintain its quality. After the necessary research data is obtained from primary or secondary data, the data is calculated as thermal using the LMTD (Log Mean Temperature Difference) method, which is the logarithmic average of the temperature ratio between the fluid to be cooled and the fluid to cool. From the results of calculations before repairs were obtained LMTD values of 2,325 ° C, 2,814 ° C, 2,926 ° C, 2,029 ° C, 2,741 ° C before repairs and obtained 2,245 ° C, 1,529 ° C, 2,231 ° C, 1,529 ° C, 1,581 ° C after repairs. If the LMTD value rises, then the heat dissipated will decrease. Meanwhile, if the LMTD value drops, the heat to be released will be even greater. After repairs on the GT CCW Cooling Fan there is a decrease in temperature in the Closed Water Cooling so that the air used to cool the Auxiliary Gas Turbine will also increase.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: GT CCW Cooler Fan, Pemeliharaan, Auxiliary Gas Turbine, Log Mean Temperature Difference GT CCW Cooler Fan, Maintenance, Auxiliary Gas Turbine,Log Mean Temperature Difference
Subjects: Skripsi
Bidang Keilmuan > Teknik Mesin
Divisions: Vokasi > D3 Teknik Mesin
Depositing User: Sudarman
Date Deposited: 14 May 2026 07:06
Last Modified: 14 May 2026 07:06
URI: https://repository.itpln.ac.id/id/eprint/6737

Actions (login required)

View Item
View Item