Akbar, Irsyad and Diantari, Retno Aita (2025) Analisis Karakteristik Tegangan Tembus Minyak Kelapa Sebagai Alternatif Pengganti Minyak Transformator Dengan Tambahan Zat Aditif Butylated Hydroxytoluene (BHT). Diploma thesis, Institut Teknologi PLN.
SKRIPSI 202111210 IRSYAD AKBAR.pdf
Restricted to Registered users only
Download (3MB)
Abstract
Mineral oil is the most widely used oil in the world of electric power, especially in insulating oil. This study aims to analyze alternatives to mineral oil that are more environmentally friendly so that the availability of mineral oil in the earth is still maintained.The research conducted uses breakdown voltage testing on coconut oil as an
alternative to transformer insulation oil with the addition of Butylated Hydroxytoluene additives. After testing the breakdown voltage, the dielectric calculation is analyzed using the available formula. The breakdown voltage test was carried out using the BAUR DPA 75 Oil Breakdown Tester tool located at the High Voltage Equipment Technology Laboratory at the PLN Institute of Technology. From this study, the highest breakdown voltage value was obtained in the coconut oil test with 5% Butylated Hydroxytoluene additive, with an average breakdown voltage value of 54.6 kV/2.5 mm. According to PLN Standard 49-1:1982, this value exceeds the minimum breakdown voltage specified, which is 30 kV/2.5 mm. The lowest breakdown voltage was observed in the coconut oil test with Shell Dila B mineral oil additive, with a breakdown voltage of 16.25 kV/2,5 mm.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Insulating oil, Coconut oil, Breakdown voltage, Transformer, Additives |
| Subjects: | Bidang Keilmuan > Oil Skripsi Bidang Keilmuan > Transformer Oil |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |