Nosi, Vicario Sillarts and Suyanto, Heri (2025) PERENCANAAN SISTEM KELISTRIKAN UNTUK MENGATASI TERJADINYA DROP TEGANGAN DAN THD PADA PROYEK PERUMAHAN CLUSTER R30 KOTA BARU PARAHYANGAN. Diploma thesis, Institut Teknologi PLN.
![[thumbnail of SKRIPSI 202211584 VICARIO SILLARTS NOSI.pdf]](https://repository.itpln.ac.id/style/images/fileicons/text.png)
SKRIPSI 202211584 VICARIO SILLARTS NOSI.pdf
Restricted to Repository staff only
Download (2MB)
Abstract
Perencanaan system kelistrikan pada proyek perumahan Cluster R30 Kota Baru Parahyangan ini membahas perencanaan sistem kelistrikan untuk mengatasi drop tegangan dan Total Harmonic Distortion (THD) pada proyek perumahan Cluster R30 Kota Baru Parahyangan. Tujuan utama penelitian ini adalah menghitung nilai drop tegangan dan THD pada setiap feeder, mengidentifikasi penyebabnya, serta merancang solusi untuk menjaga kualitas daya sesuai standar yang berlaku. Perhitungan dilakukan secara manual dan menggunakan perangkat lunak ETAP. Hasil simulasi menunjukkan bahwa nilai drop tegangan terbesar adalah 1,8%, sementara nilai terkecil 0,2%, yang masih sesuai dengan standar SPLN 72:1987 (maksimal 5%). Untuk mengurangi drop tegangan, digunakan penghantar berpenampang besar, distribusi beban merata, dan pengaman berkualitas. Nilai THD yang dihitung menunjukkan THD arus sebesar 151% dan THD tegangan 7,04%, melebihi batas standar IEEE STD 519-2014 (THD arus maksimal 20% dan THD tegangan maksimal 5%). Solusi yang diterapkan untuk mengurangi THD adalah kombinasi Active Power Filter (APF) dan filter pasif LC tuned, yang berhasil menurunkan THD tegangan menjadi 6,04%. Meskipun belum sepenuhnya sesuai standar, kombinasi ini secara signifikan meningkatkan kualitas daya listrik. Penelitian ini menyimpulkan bahwa pendekatan perencanaan yang terstruktur dan penggunaan perangkat mitigasi harmonik dapat meningkatkan stabilitas dan kualitas sistem kelistrikan, sehingga layak diterapkan pada proyek perumahan berskala besar.
This electrical system planning in the Cluster R30 Kota Baru Parahyangan housing project discusses electrical system planning to overcome voltage drop and Total Harmonic Distortion (THD) in the Cluster R30 Kota Baru Parahyangan housing project. The main objective of this research is to calculate the voltage drop and THD values on each feeder, identify the causes, and design solutions to maintain power quality according to applicable standards. Calculations are done manually and using ETAP software. The simulation results show that the largest voltage drop value is 1.8%, while the smallest value is 0.2%, which is still in accordance with the SPLN 72:1987 standard (maximum 5%). To reduce voltage drop, large-section conductors, even load distribution, and quality safety are used. The calculated THD values show a current THD of 151% and a voltage THD of 7.04%, exceeding the IEEE STD 519- 2014 standard limits (maximum current THD of 20% and maximum voltage THD of 5%). The solution implemented to reduce THD was a combination of Active Power Filter (APF) and LC tuned passive filter, which successfully lowered the voltage THD to 6.04%. Although not yet fully compliant, this combination significantly improved the quality of electrical power. This research concludes that a structured planning approach and the use of harmonic mitigation devices can improve the stability and quality of the electrical system, making it feasible to apply to large-scale residential projects.
Item Type: | Thesis (Diploma) |
---|---|
Uncontrolled Keywords: | Drop Tegangan, THDI, THDV, ETAP, Filter Harmonik. Voltage Drop, THDI, THDV, ETAP, Harmonic Filter. |
Subjects: | Bidang Keilmuan > Electrical Engineering Skripsi Bidang Keilmuan > Teknik Elektro |
Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
Depositing User: | Budi Herdiansyah |