SYAMARTA, MONICA and Pramono, Tri Joko (2025) ANALISIS PENGARUH DOUBLE GROUNDING PADA RANGKAIAN SECONDARY CURRENT TRANSFORMER TERHADAP GANGGUAN PHASA TANAH: STUDI KASUS GANGGUAN HILANG TEGANGAN DI GARDU INDUK 150KV ULUBELU. Diploma thesis, Institut Teknologi PLN.
SKRIPSI 202211619 MONICA SYAMARTA.pdf
Restricted to Registered users only
Download (7MB)
Abstract
Penelitian ini bertujuan untuk menganalisa pengaruh double grounding pada rangkaian sekunder Current Transformer (CT) terhadap gangguan phasa tanah di Gardu Induk 150KV Ulubelu. Grounding yang tidak tepat dapat menyebabkan fluktuasi potensial yang mengganggu pembacaan arus netral, berpotensi mengakibatkan malakerja pada relay proteksi. Metode penelitian ini meliputi pengumpulan data dari pengukuran arus sebelum dan sesudah perbaikan grounding, serta analisis terhadap pembacaan arus netral dari relay proteksi yang terpasang. Hasil penelitian menunjukkan bahwa adanya double grounding menyebabkan pembacaan arus netral yang tidak akurat yang mengakibat lonjakan nilai pembacaan arus netral, hal ini berkontribusi pada gangguan trip pada Trafo Daya 150KV/20KV. Setelah perbaikan dilakukan, pembacaan arus netral menunjukkan nilai sesuai dengan keadaaan sistem dan tidak ada lagi lonjakan arus netral, mengkonfirmasi bahwa pemasangan grounding yang benar dengan memastikan hanya satu titik grounding (single grounding) pada setiap core Current Transformer (CT) sangat penting untuk menjaga keandalan sistem kelistrikan. Penelitian ini diharapkan dapat memberikan kontribusi meningkatkan pemahaman mengenai pentingnya grounding yang tepat dalam sistem kelistrikan.
This research aims to analyze the effect of double grounding on the secondary circuit of the Current Transformer (CT) concerning ground phase faults at the 150 kV Ulubelu Substation. Improper grounding can cause potential fluctuations that disrupt neutral current readings, potentially leading to malfunctions in protection relays. The research methodology includes data collection from current measurements before and after grounding improvements, as well as an analysis of the neutral current readings from the installed protection relays. The results indicate that double grounding leads to inaccurate neutral current readings, causing spikes in the neutral current values, which contributes to trip faults in the 150 kV/20 kV power transformer. After improvements were made, the neutral current readings aligned with the system's conditions, and there were no further spikes in the neutral current, confirming that proper grounding installation—ensuring a single grounding point for each core of the Current Transformer (CT)—is crucial for maintaining the reliability of electrical systems. This research is expected to contribute to a better understanding of the importance of proper grounding in electrical systems.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Double Grounding, Current Transformer, Gangguan Phasa Tanah, Gardu Induk, Arus Netralix Double Grounding, Current Transformer, Ground Phase Faults, Substation, Neutral Current |
| Subjects: | Bidang Keilmuan > Electrical Engineering Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Budi Herdiansyah |
| Date Deposited: | 08 Oct 2025 02:17 |
| Last Modified: | 08 Oct 2025 02:17 |
| URI: | https://repository.itpln.ac.id/id/eprint/1917 |