Permadi, Danang Satria and Alvianingsih, Ginas (2025) ANALISA PERBAIKAN TEGANGA JATUH PADA PENYULANG PTI 13 DENGAN MAÌNUVER BEBAN KE PENYULANG PTI 7 DI SISTEM DISTRIBUSI PT. PLN (Persero) UNIT LAYANAN PELANGGAN JUWANA. Diploma thesis, Institut Teknologi PLN.
SKRIPSI 202211911 DANANG SATRIA PERMADI.pdf
Restricted to Registered users only
Download (7MB)
Abstract
Tegangan merupakan variabel yang harus dijaga nilainya agar sesuai dengan Standar PLN, yaitu SPLN No. 72 Tahun 1987, dengan jatuh tegangan -10 %, dan nilai batas atas sebesar +5 % dari tegangan nominal. Pad a Sistem Distribusi PT. PLN (Persero) ULP Juwan a terdap at penyul ang y ang memiliki teg ang an jatuh y ang sang at tinggi, yaitu Penyulang PTI -13. Faktor penyebab terjadinya tegangan jatuh, diantaranya panjang jaringan, luas penampang jaringan, reaktansi dan resistansi jenis konduktor. Skripsi ini mempunyai tujuan, yaitu memperbaiki tegangan jatuh pada Penyulang PTI-13 yang memiliki beban yang besar serta panjang jaringan yang paling panjang diantara Penyulang lainnya. Metode yang diguanakan dalam perbaikan tegangan jatuh pada Penyulang PTI-13, yaitu denganmanuver beban atau pecah beban, dengan memindahkan sebagian beban penyulang PTI-13 ke Penyulang yang memiliki beban kecil, dan dengan mengganti jenis penghantar yang digunakan pada penyulang PTI-13. Sebelum dilakukan simulasi nilai tegangan jatuh pada kondisi eksisting penyulang PTI-13 adalah 3,426 kV, dan setelah dilakukan pengujian dengan simulasi diperoleh hasil bahwa setelah dilakukan manuver beban, nilai tegangan jatuh pada penyulang PTI-13 semula 3,565 kV, dengan penurunan tegangan jatuh sebesar 1,121 kV. Dilakukan penggantian jenis dan luas penampang penghantar pada Penyulang PTI-13 dengan mengganti jenis penghantar XLPE dengan luas penampang penghantar sebesar 240 cm2. Sehingga didapatkan nilai jatuh tegangan menjadi 1,285 kV, dan nilai tegangan menjadi 18,715 kV.
Voltage is a variable that must be maintained to comply with the PLN Standard, namely SPLN No. 72 of 1987, with a voltage drop of -10%, and an upper limit value of +5% of the nominal voltage. In the Distribution System of PT. PLN (Persero) ULP Juwana, there is a feeder that has a very high voltage drop, namely the PTI-13 Feeder. Factors that cause voltage drops include network length, network cross-sectional area, reactance and conductor type resistance. This thesis has the aim of improving the voltage drop on the PTI-13 Feeder which has a large load and the longest network length among other Feeders. The method used to improve the voltage drop on the PTI-13 Feeder is by maneuvering the load or breaking the load, by moving part of the PTI-13 feeder load to the Feeder that has a small load, and by replacing the type of conductor used on the PTI-13 feeder. Before the simulation, the voltage drop value in the existing condition of the PTI-13 feeder was 3.426 kV, and after testing with simulation, the results showed that after the load maneuver, the voltage drop value in the PTI-13 feeder was originally 3.565 kV, with a decrease in voltage drop of 1.121 kV. The type and cross-sectional area of the conductor in the PTI-13 feeder were replaced by replacing the type of XLPE conductor with a conductor cross-sectional area of 240 cm². So that the voltage drop value is 1.285 kV, and the voltage value is 18.715 kV.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Tegangan, Tegangan Jatuh, Penyulang, Manuver Bebani Voltage, Voltage Drop, Feeder, Load Maneuver |
| Subjects: | Bidang Keilmuan > Electrical Engineering Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Budi Herdiansyah |
| Date Deposited: | 13 Oct 2025 00:59 |
| Last Modified: | 13 Oct 2025 00:59 |
| URI: | https://repository.itpln.ac.id/id/eprint/2060 |