Nadia, Lut Alfia Nur and Senen, Adri (2025) ANALISIS KEGAGALAN TRANSFORMATOR BERDASARKAN HASIL UJI DISSOLVED GAS ANALYSIS (DGA) DENGAN METODE TDCG, KEY GAS, DAN DUVAL TRIANGLE DI GI BOGOR BARU 150 kV. Diploma thesis, Institut Teknologi PLN.
SKRIPSI 202211919 LUT ALFIA NUR NADIA.pdf
Restricted to Registered users only
Download (9MB)
Abstract
Transformator merupakan komponen vital dalam sistem kelistrikan yang berperan mengubah tegangan listrik untuk distribusi yang efisien. Normal usia transformator berdasarkan IEC 60354-1 tahun 1991 dan SPLN tahun 2017 adalah 20 tahun. Deteksi dini potensi kegagalan merupakan peran penting pada pengoperasian sistem tenaga listrik yang andal dan memaksimalkan usia transformator. Salah satu metode pengujian kegagalan transformator adalah DGA (Dissolved Gas Analysis) dengan mengukur konsentrasi fault gases pada minyak transformator. Dengan menganalisa hasil uji DGA pada transformator yang ada di Gardu Induk Bogor Baru menggunakan metode TDCG, key gas dan duval triangle, diketahui kondisi Transformator 3 dan Transformator 6 dalam kondisi sehat, namun terindikasi partial discharge. Sementara Transformator 4 dan Transformator 5 terindikasi gangguan thermal diatas 700º C yaitu overheat pada selulosa. Koefisien korelasi (r) fault gases (TDCG) berdasarkan hasil uji DGA dengan Waktu operasi transformator sebesar 0,66 pada Transformator 3, sebesar -0,71 pada Transformator 4, sebesar -0,27 pada Transformator 5, dan sebesar 0,58 pada Transformator 6.
Transformers are vital components in the electrical system that play a role in changing the electrical voltage for efficient distribution. The normal life of a transformer based on IEC 60354-1 in 1991 and SPLN in 2017 is 20 years. Early detection of potential failure plays an important role in the operation of a reliable electric power system and maximizing the life of the transformer. One method of testing transformer failure is DGA (Dissolved Gas Analysis) by measuring the concentration of fault gases in transformer oil. By analyzing the results of the DGA test on the transformers in the Bogor Baru Substation using the TDCG, key gas and duval triangle methods, it is known that the conditions of Transformer 3 and Transformer 6 are in good condition, but are indicated as partial discharge. Meanwhile, Transformer 4 and Transformer 5 are indicated as thermal disturbances above 700º C, namely overheating of cellulose. The correlation coefficient (r) of fault gases (TDCG) based on the results of the DGA test with the transformer operating time is 0.66 on Transformer 3, -0.71 on Transformer 4, -0.27 on Transformer 5, and 0.58 on Transformer 6.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Transformator, DGA, TDCG, Key Gas, Duval Triangle Transformer, DGA, TDCG, Key Gas, Duval Triangle |
| Subjects: | Bidang Keilmuan > Electrical Engineering Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Budi Herdiansyah |
| Date Deposited: | 13 Oct 2025 02:19 |
| Last Modified: | 13 Oct 2025 02:19 |
| URI: | https://repository.itpln.ac.id/id/eprint/2080 |