Abstract

Tumbuhnya industri saat ini menuntut pasokan energi yang cukup besar, di mana PLTU menjadi salah satu penyedia utama energi listrik di Indonesia. PT. Indonesia Power JABAR 2 Palabuhan Ratu adalah salah satu pembangkit yang berperan dalam menyuplai listrik di Jawa Barat. Kinerja PLTU dipengaruhi oleh komponen utama, termasuk kondensor, yang memiliki peran vital dalam siklus rankine sehingga kondensor perlu dijaga keoptimalannya. Tujuan dari penelitian ini adalah untuk mengetahui perubahan tekanan yang terjadi pada kondensor setelah dilakukannya pemasangan strainer yang nantinya berpengaruh terhadap efektivitas kondensor. Dimana dalam penelitian ini meliputi perhitungan LMTD, laju perpindahan panas, dan efektivitas kondensor. Diperoleh hasil setelah dilakukannya pemasangan strainer berdampak positif dimana kenaikan nilai efektivitas dari 47% menjadi 50 % pada beban 55% dengan tekanan 704,83 mmHg menjadi -705,08 mmHg. Efektivitas kondensor mengalami kenaikan sebesar 1.81%. Dimana, ketika nilai vakum semakin rendah maka mampu mempengaruhi efektivitas kondensor, semakin rendah nilai vakum akan mempengaruhi nilai laju perpindahan panas yang akan semakin kecil dan nilai LMTD mengalami penurunan sebesar 0.36 ˚C sehingga nilai efektivitas kondensor meningkat. Kinerja kondensor dipengaruhi oleh tekanan vakum, kebersihan tube,pemeliharaan, kualitas dan suhu air pendingin, dan pengoperasian komponen pendukung kondensor.

The growth of industry today demands a large supply of energy, where PLTU is one of the main providers of electrical energy in Indonesia. PT Indonesia Power JABAR 2 Palabuhan Ratu is one of the plants that plays a role in supplying electricity in West Java. PLTU performance is influenced by major components, including the condenser, which has a vital role in the Rankine cycle so that the condenser needs to be maintained optimally. The purpose of this study is to determine the pressure changes that occur in the condenser after the installation of strainers which will affect the effectiveness of the condenser. Where in this study includes the calculation of LMTD, heat transfer rate, and condenser effectiveness. The results obtained after the installation of the strainer have a positive impact where the effectiveness value increases from 47% to 50 % at 55% load with a pressure of -704.83 mmHg to -705.08 mmHg. The effectiveness of the condenser has increased by 1.81%. Where, when the vacuum value is lower, it can affect the effectiveness of the condenser, the lower the vacuum value will affect the value of the heat transfer rate which will be smaller and the LMTD value decreases by 0.36 ˚C so that the condenser effectiveness value increases. Condenser performance is influenced by vacuum pressure, tube cleanliness, maintenance, cooling water quality and temperature, and operation of condenser support components.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: PLTU, Kondensor, Tekanan vakum, Efektivitas PLTU, Condenser, Vacuum pressure, Effectiveness
Subjects: Skripsi
Bidang Keilmuan > Teknik Mesin
Divisions: Fakultas Teknologi dan Bisnis Energi > S1 Teknik Mesin
Depositing User: Nurul Hidayati
Date Deposited: 27 Aug 2025 03:58
Last Modified: 27 Aug 2025 03:58
URI: https://repository.itpln.ac.id/id/eprint/221

Actions (login required)

View Item
View Item