Nursal, Eviyana and dini, hasna satya (2022) KOORDINASI RELAY ARUS LEBIH (OCR) DAN RELAY DIFFERENSIAL PADA TRANSFORMATOR DAYA KAPASITAS 60 MVA GARDU INDUK CIPINANG 150/20 KV. Diploma thesis, ITPLN.
SKRIPSI 202011307 EVIYANA NURSAL.pdf
Restricted to Registered users only
Download (5MB)
Abstract
Gardu Induk Cipinang memiliki transformator daya dengan kapasitas 60 MVA yang terdiri dari beberapa sistem peroteksi yakni 1 relay differensial dan 2 relay arus lebih (OCR). Dalam menjamin keandalan pasokan daya pada pelanggan maka diperlukan sebuah proteksi yang mampu bekerja optimal agar pasokan listrik sampai ke konsumen tanpa adanya kendala ataupun gangguan. Agar hal seperti ini dapat dicegah atau diminimalisir maka dibutuhkan setting proteksi relay dan setting koordinasi antara relay differensial dan relay arus lebih yang baik dan benar agar mampu melindungi transformator dari gangguan hubung singkat dan arus lebih. Hasil analisis yang dilakukan menggambarkan untuk relay differensial bekerja sebagai proteksi utama apabila terjadi gangguan di dalam daerah proteksi transformator dan untuk relay arus lebih dapat menjadi proteksi utama jika terjadi gangguan di luar daerah proteksi transformator. Setelah melakukan perhitungan didapat arus setting primer OCR untuk sisi 150 kV sebesar 277.2 A dan sisi 20 kV sebesar 2078.4 A dengan nilai TMS sisi 150 kV adalah 0.075 A dan nilai TMS sisi 20 kV adalah 0.175 A, sedangkan untuk nilai setting relay differensial sebesar 0.16 A dan setelah dilakukan simulasi hubung singkat 3 fasa menggunakan aplikasi ETAP koordinasi relay berjalan dengan optimal.
The Cipinang Substation has a power transformer with a capacity of 60 MVA which consists of several protection systems, namely 1 differential relay and 2 overcurrent relays (OCR). In ensuring the reliability of power supply to customers, a protection that is able to work optimally is needed so that the electricity supply reaches consumers without any obstacles or disturbances. So that things like this can be prevented or minimized, it is necessary to set relay protection and coordination settings between differential relays and overcurrent relays that are good and correct in order to be able to protect transformers from short-circuit and overcurrent disturbances. The results of the analysis carried out illustrate that the differential relay works as the main protection in the event of a disturbance in the transformer protection area and for the overcurrent relay it can be the main protection in the event of a disturbance outside the transformer protection area. After doing the calculations, the OCR primary setting current for the 150 kV side is 277.2 A and the 20 kV side is 2078.4 A with the TMS value for the 150 kV side is 0.075 A and the TMS value for the 20 kV side is 0.175 A, while the differential relay setting value is 0.16 A. and after a 3-phase short circuit simulation using the ETAP application, the relay coordination runs optimally.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Transformator Daya, Gardu Induk, Koordinasi Relay, Relay Arus Lebih, Relay Differensial Power Transformer, Substation, Coordination Relay, Overcurrent Relay, Differential Relay |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 17 Oct 2025 07:31 |
| Last Modified: | 17 Oct 2025 07:31 |
| URI: | https://repository.itpln.ac.id/id/eprint/2518 |