ANALISIS SUSUT UMUR MAIN TRAFO 34 MVA BERDASARKAN PENGUJIAN MINYAK DI PLTU JERANJANG OMU LOMBOK NUSA TENGGARA BARAT

Rasuani, Nadya Fadhilah and Pahiyanti, Novi Gusti (2022) ANALISIS SUSUT UMUR MAIN TRAFO 34 MVA BERDASARKAN PENGUJIAN MINYAK DI PLTU JERANJANG OMU LOMBOK NUSA TENGGARA BARAT. Diploma thesis, ITPLN.

[thumbnail of SKRIPSI 201811224 NADYA FADHILAH RASUANI.pdf] Text
SKRIPSI 201811224 NADYA FADHILAH RASUANI.pdf
Restricted to Registered users only

Download (3MB)

Abstract

Proses penyaluran tenaga listrik di jaringan baik distribusi maupun transmisi membutuhkan transformator dimana diharapkan transformator tersebut dapat dioperasikan secara maksimal dan efisien dalam kurun waktu yang panjang. Belitan merupakan komponen utama dari transformator yang berguna untuk mentransformasikan energi. Belitan tersebut diisolasi dengan kertas lalu direndam oleh minyak. Evaluasi kondisi dari isolasi kertas transformator merupakan salah satu asesmen penting dalam penilaian kondisi sebuah transformator karena sistem isolasi kertas mengalami penuaan yang irreversible. Melalui penelitian ini, umur transformator diselediki berdasarkan konsentrasi furan yang terkandung dalam minyak menggunakan metode kuantitatif dengan teknik analisis deskriptif. Dengan mengacu pada standar IEEE C57.140 Tahun 2017 dan IEEE 45 Tahun 2002, didapatkan hasil bahwa Main Trafo Unit 1 dan Main Trafo Unit 2 di PLTU Jeranjang masing masing berumur 3,8 tahun dan 2,4 tahun dengan sisa masa pakai masing masing 16,6 tahun dan 18,1 tahun. Dari hasil tersebut dapat disimpulkan bahwa kedua transformator tersebut dalam kondisi yang sangat baik dan dapat beroperasi lebih lanjut.

The process of distributing electric power in the network, both distribution and transmission, requires a transformer where it is expected that the transformer can be operated optimally and efficiently over a long period of time. Windings are the main component of transformers that are useful for transforming energy. The winding is insulated with paper and then soaked by oil. Evaluation of the condition of transformer paper insulation is one of the important assessments in the assessment of the condition of a transformer because the paper insulation system is irreversible aging. Through this study, the life of the transformer was reduced based on the concentration of furan contained in the oil using quantitative methods with descriptive analysis techniques. With reference to the standards of IEEE C57,140 of 2017 and IEEE 45 of 2002, it was found that the Main Transformer Unit 1 and Main Transformer Unit 2 at PLTU Jeranjang are 3.8 years old and 2.4 years old respectively with the remaining service life of each . From these results it can be concluded that both transformers are in excellent condition and do not need replacement.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Transformator, Analisis Furan, Susut Umur Transformer, Furan Analysis, Lifetime
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro