Haloho, Luwis Surani and Pramono, Tri Joko (2022) ANALISA PENGUJIAN KARAKTERISTIK TIIERMAL OVERLOAD RELAY MENGGUNAKAN CMC 356 DI pT. pLN (PERSERO) PUSAT SERTIFTKASI DI'RENTIGA. Diploma thesis, ITPLN.
SKRIPSI 201811240 LUWIS SURANI HALOHO.pdf
Restricted to Registered users only
Download (4MB)
Abstract
Pengujian Thermal Overload Relay ini merupakan salah satu pengujian produk pada sistem tenaga listrik khususnya system proteksi. Pengujian ini dilakukan untuk menilai kualitas sesuai metode dan kriteria berdasarkan Test Specification thermal and thermal TDL relay base IEC 60255-149 oleh PLN Pusat Sertifikasi. Dengan metode kuntitatif eksperimental pada saat dilakukan pengujian yaitu mengatur nilai variabel yang akan diuji dan komparatif untuk mengetahui hasil uji dengan membandingkan nilai hasil uji dan hasil perhitungan. Pada akurasi nilai arus operasi thermal Overload Relay yang di uji yaitu tidak mengalami trip selama waktu uji dan thermal level bernilai <100 %, pengujian waktu kerja tanpa beban 0% memenuhi standar dengan error belum melampaui standar, Pada akurasi waktu kerja di beri beban dengan mengatur level preload 10 %, 30%, 50%,70% dan 90% dihasilkan waktu kerja yang tidak melebihi ketentuan, Pada kinerja pengaruh dari harmonik 10% harmonik ke-3, 25% harmonik ke-5 dan 15% harmonik ke-7 masih memenuhi kriteria, kinerja variasi frekuensi pengujian ini walaupun diberikan variasi frekuensi dengan mengatur sebesar 45 Hz dan 55 tidak mempengaruhi dari waktu kerja relai apabila besar arus operasi dan waktu pengujian dengan waktu yang sama
One of the product tests for the electrical power system, particularly the protective system, is this Thermal Overload Relay test. This test is conducted by the PLN Certification Center to evaluate the quality in accordance with the standards and parameters based on the Thermal Test Specification and the IEC 60255-149 thermal TDL relay basis. Using the experimental quantitative approach, which involves establishing the value of the test variable and comparing it to the results of the computation, one can determine the test results. The test depends on the reliability of the thermal operating current value of the relay under test, that is, on the fact that it does not trip during the test and that the thermal level is practicable at 100%. When the accuracy of the working time is charged by setting the level preload at 10%, 30%, 50%, 70%, and 90%, the resulting working time does not exceed the provisions, the test of working time without a load of 0% satisfies the standard with the error not exceeding the standard. The performance of this test frequency variation, even though given a frequency variation with 45 Hz and 55 time settings, does not affect the relay working time if the operating current and testing time are the same. However, the influence of the 10 percent harmonic third harmonic, 25 percent harmonic fifth harmonic, and 15 percent harmonic seventh harmonic are still requirements.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | sistem proteksi,Pengujian,Thermal Overload Relay Thermal Overload Relay, testing, and protective system |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |