Abstract

Relay Differentian digunakan ketika terlihat adanya gangguan yang membuat aliran listrik yang mengalir ke konsumen menjadi terganggu. Dapat diketahui jika transformator mengalami gangguan maka phal yang sangay dibutuhkan ialah sebuat proteksi. Salaha satunya dengan penyusunan renana kepada relay differential, relay differential merupakan relay yang memiliki sifat andal, selektif fan cepat dalam bekerja ketika penyettingan nya dilakukan secara optimal. Pembahasan pada skripsi ini ialah memperhitungkan setting relay differential secara teori serta mendapatkan topic penyettingan pada GI Karet Lama. Saat membuat tugas akhir ini penulis menggunakan metode penelitian kuantitatif yang dimulai dari pengumpulan data,pengolahan data, hingga hasil tersebut dapat di analisa mulai dari nilai slope 1 sebesar 11,76% dan slope 2 sebesar 23,52% sehingga di dapat arus penyettingan sebesar 0,0964 A untuk nilai slope 1 yang digunakan pada gardu induk Karet Lama sebesar 30% dan untuk nilai slpoe 2 sebesar 80%. untuk rasio pada sisi pada CT 150 kV yang digunakan adalah 300:1 serta pada sisi tegangan 20 kV arus nominal yang di dapat sebesar 1732,05081 A dan nilai arus rating di dapat sebesar 1905,25589 A oleh karena itu rasio CT yang digunakan sebesar 2000:51A.

Differentian relays are used when there is a disturbance that disrupts the flow of electricity flowing to consumers. It can be seen if the transformer has a fault then the thing that is really needed is a protection. One of them is the preparation of plans for differential relays, differential relays are relays that have reliable properties, selective fans are fast in working when the settings are carried out optimally. The discussion in this thesis is to calculate the theoretical differential relay setting and to get the topic of setting the GI Karet Lama. When making this final project the author uses quantitative research methods starting from data collection, data processing, so that the results can be analyzed starting from the slope 1 value of 11.76% and slope 2 of 23.52% so that the setting current is 0 .0964 A for the value of slope 1 used at the Old Karet substation is 30% and for the value of slpoe 2 is 80%. for the ratio on the 150 kV CT side used is 300:1 and on the 20 kV voltage side the nominal current obtained is 1732.05081 A and the rated current value is 1905.25589 A, therefore the CT ratio used is 2000 :51A.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Relay Differential, Proteksi, CT Relay Differential, Protection, CT
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 20 Oct 2025 08:27
Last Modified: 20 Oct 2025 08:27
URI: https://repository.itpln.ac.id/id/eprint/2616

Actions (login required)

View Item
View Item