Adriatama, Arung and Pramono, Tri Joko (2022) ANALISIS KETIDAKSEIMBANGAN BEBAN PADA TRANSFORMATOR GARDU INDUK PUNCAK ARDI MULYA 150/20 KV AREA BANTEN. Diploma thesis, ITPLN.
SKRIPSI 201811214 ARUNG ADRIATAMA.pdf
Restricted to Registered users only
Download (2MB)
Abstract
Ketidakseimbangan beban pada trafo distribusi tenaga listrik selalu terjadi dan ketidakseimbangan tersebut terjadi karena ketidaksamaan pemakaian energi listrik. Akibat ketidakseimbangan beban tersebut mengalir arus di netral trafo. Arus yang mengalir di penghantar netral trafo ini menyebabkan terjadinya ketidak seimbangan beban trafo, rugi-rugi, yaitu rugi akibat adanya arus netral pada penghantar netral trafo. Rugi-rugi yang terdapat pada trafo adalah rugi daya, rugi inti dan rugi tembaga. Dalam menganalisis masalah menggunakan model matematis meliputi persamaan ketidakseimbangan beban trafo, rugi- rugi daya dan efisiensi. Setelah dianalisis menunjukkan bahwa trafo dalam keadaan tidak seimbang dimana bila terjadi ketidakseimbangan beban yang besar, maka arus netral yang muncul juga besar. Efisiensi trafo akan semakin besar jika selisih daya masuk dan daya keluar kecil. Presentase pembebanan Transformator satu sebesar 22,5% dan Trafo dua sebesar 5,14 ketidakseimbangan beban lebih besar pada malam hari yaitu pada Trafo satu sebesar 187% dan Trafo dua sebesar 2,66 %.
Unbalance in the load on the electric power distribution transformer always occurs and the imbalance occurs because of the unequal use of electrical energy. Due to the load imbalance, current flows in the neutral of the transformer. The current flowing in the neutral conductor of this transformer causes an imbalance in the transformer load, losses, namely losses due to the neutral current in the transformer neutral conductor. The losses contained in the transformer are power loss, core loss and copper loss. In analyzing the problem using a mathematical model includes the transformer load imbalance equation, power losses and efficiency. After being analyzed, it shows that the transformer is in an unbalanced state where if there is a large load imbalance, the neutral current that appears is also large. The efficiency of the transformer will be even greater if the difference between incoming and outgoing power is small. The percentage of loading on Transformer one is 22.5% and Transformer two is 5.14. The load imbalance is bigger at night, that is, Transformer one is 187% and Transformer two is 2.66%.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Ketidakseimbangan beban, rugi-rugi daya dan arus netral Unbalance load, power losses and neutral current |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 21 Oct 2025 04:02 |
| Last Modified: | 21 Oct 2025 04:02 |
| URI: | https://repository.itpln.ac.id/id/eprint/2656 |