Felicia, Asti and Hutajulu, Gifson Albert (2022) ANALISIS KUALITAS ISOLASI PADA TRANSFORMATOR DAYA UAT (Unit Auxiliary Transformer ) 11,5/6,3 KV Unit 1 DENGAN PENGUJIAN TANGEN DELTA DI PT PLN (PERSERO) UPK OMBILIN 2X100 MW. Diploma thesis, ITPLN.
SKRIPSI 201811177 ASTI FELICIA.pdf
Restricted to Registered users only
Download (3MB)
Abstract
Transformator daya UAT (Unit Auxiliary Transformer) 11,5/6,3 kV adalah peralatan yang berfungsi untuk mentransformasikan tegangan sistem yang lebih tinggi ke suatu tegangan sistem yang lebih rendah untuk kebutuhan peralatan indikator, alat ukur/meter dan relai.Waktu pengoperasian mengakibatkan transformator daya UAT (Unit Auxiliary Transformer) 11,5/6,3 kV mengalami penurunan maupun kegagalan fungsi. Oleh karena itu perlu dilakukan pengujian guna mengetahui kondisi dari transformator daya UAT (Unit Auxiliary Transformer) 11,5/6,3 kV. Salah satu metode pengujian yang digunakan pada transformator daya UAT (Unit Auxiliary Transformer) 11,5/6,3 kV adalah pengujian tangen delta dimana pengujian ini berfungsi untuk mengetahui penurunan kemampuan isolasi dari suatu peralatan dan nilai kapasitansi perlatan tersebut, dalam pengujian tangen delta pada transformator ini menggunakan alat uji omicron CPC 100. Adapun faktor-faktor yang mempengaruhi nilai hasil uji tangen delta adalah suhu, kotoran, kelembaban serta kerusakan pada mekanisme transformator. Pengujian tangen delta yang dilakukan ini mengacu pada standar IEEE std C57.152-2013 yang mengatakan jika nilai tangen delta tidak melebihi 0,5% maka transformator dalam keadaan baik. Jika nilai tangen delta 0,5%-1% masih dapat di toleransi.Jika nilai tangen delta >1% maka kualitas isolasi pada transformator mengalami penurunan.
A 11.5/6.3 kV UAT (Unit Auxiliary Transformer) power transformer is equipment that functions to transform a higher system voltage to a lower system voltage for the needs of indicator equipment, measuring instruments/meters and relays. UAT (Unit Auxiliary Transformer) power of 11.5/6.3 kV has decreased or malfunctioned. Therefore, it is necessary to conduct a test to determine the condition of the 11.5/6.3 kV UAT (Unit Auxiliary Transformer) power transformer. One of the test methods used on the 11.5/6.3 kV UAT (Unit Auxiliary Transformer) power transformer is the tangent delta test where this test serves to determine the decrease in the insulation ability of an equipment and the value of the capacitance of the equipment, in the delta tangent test at This transformer uses the Omicron CPC 100 test equipment. The factors that affect the value of the tangent delta test results are temperature, dirt, humidity and damage to the transformer mechanism. The delta tangent test carried out refers to the IEEE std C57.152-2013 standard which says if the delta tangent value does not exceed 0.5% then the transformer is in good condition. If the tangent delta value is 0.5%-1% it can still be tolerated. If the tangent delta value is >1% then the insulation quality of the transformer has decreased.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Tangen Delta, Transformator Daya UAT, Isolasi. Tangent Delta, UAT Power Transformer, Isolation. |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 21 Oct 2025 07:15 |
| Last Modified: | 21 Oct 2025 07:15 |
| URI: | https://repository.itpln.ac.id/id/eprint/2700 |