ANALISIS PREDIKSI SISA UMUR GENERATOR DENGAN MELAKUKAN PENGUJIAN DIELEKTRIK PADA STATOR GENERATOR PLTU OMBILIN UNIT 2 PT PLN (PERSERO)

SAPUTRI, NIKEN PRADINA and Fernandes, Alex (2022) ANALISIS PREDIKSI SISA UMUR GENERATOR DENGAN MELAKUKAN PENGUJIAN DIELEKTRIK PADA STATOR GENERATOR PLTU OMBILIN UNIT 2 PT PLN (PERSERO). Diploma thesis, ITPLN.

[thumbnail of SKRIPSI 201811178 NIKEN PRADINA SAPUTRI.pdf] Text
SKRIPSI 201811178 NIKEN PRADINA SAPUTRI.pdf
Restricted to Registered users only

Download (2MB)

Abstract

Kebutuhan akan energi listrik yang semakin tinggi setiap tahunnya, maka dari itu diperlukan keandalan dalam menyalurkan energi listrik kepada konsumen, untuk mewujudkan keandalan tersebut diperlukan peralatan listrik yang dapat bekerja dengan baik agar tidak terjadinya kendala dalam sistem pengoperasiannya, salah satu peralatan listrik yang memiliki peranan yang sangat penting dalam pembangkit listrik tenaga uap adalah generator, seiring dengan usia pemakaian generator yang sudah lebih dari 20 tahun di PLTU Ombilin pasti mengalami beberapa kendala termasuk dalam isolasinya yang dapat menyebabkan kebocoran arus dan kerusakan total pada generator. Tujuan dilakukannya pengujian dielektrik. Penelitian ini dilakukan untuk memprediksi sisa umur dari generator karena adanya masalah dielektri yang terjadi pada sistem isolasinya dengan melakukan pengujian dielektrik dapat memprediksi sisa umur dari generator unit 2 PLTU Ombilin. Metode yang digunakan dalam penelitian ini dengan menggunakan metode D-MAP dengan formula yang digunakan dari nilai yang didapatkan dalam pengujian dielektrik, seperti pengujian tan delta, pengujian arus bocor, dan pengujian partial discharge . Hasil dari pengujian dielektrik ini mendapatkan tegangan tembus sebesar 42,48% dan mendapatkan hasil prediksi sisa umur pada generator 4 tahun lagi. Dan untuk memperbaiki nilai tegangan tembus dilakukan revarnish atau resin untuk memperbaiki nilai partial discharge nya

The need for electrical energy is getting higher every year, therefore reliability is needed in distributing electrical energy to consumers, to realize this reliability, electrical equipment that can work properly is needed so that there are no obstacles in the operating system, one of the electrical equipment that has a very important role very important in a steam power plant is the generator, along with the age of use of the generator which has been more than 20 years at the Ombilin PLTU, there must be some obstacles including its isolation which can cause current leakage and total damage to the generator. The purpose of the dielectric test. This research was conducted to predict the remaining life of the generator due to dielectric problems that occur in the insulation system by conducting dielectric tests and finding solutions to extend the life of the generator. The method used in this study using the D-MAP method with the formula used from the values obtained in dielectric testing, such as tan delta testing, leakage current testing, and partial discharge testing. The results of this dielectric test get a breakdown voltage of 42.48% and get a prediction of the remaining life of the generator for another 4 years. And to improve the breakdown voltage value, a revarnish is carried out to improve the partial discharge value

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Generator, isolasi,tan delta, arus bocor, partial discharge Generator, Dielectric, isolation,tan delta, partial discharge
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 21 Oct 2025 07:20
Last Modified: 21 Oct 2025 07:20
URI: https://repository.itpln.ac.id/id/eprint/2702