Muttaqin, Muhammad and Widyastuti, Christine (2022) ANALISIS EFEKTIVITAS GENERATOR STATOR COOLING WATER TERHADAP RUGI-RUGI DAYA YANG TIMBUL PADA STATOR GENERATOR UNIT 1 PLTU LONTAR. Diploma thesis, ITPLN.
SKRIPSI 201811099 MUHAMMAD MUTTAQIN.pdf
Restricted to Registered users only
Download (2MB)
Abstract
Dalam kehidupan sehari-hari energi listrik merupakan kebutuhan utama yang banyak dibutuhkan dan dimanfaatkan oleh manusia. Energi listrik dihasilkan oleh alat yang bernama generator, dimana generator merupakan mesin sinkron yang mengkonversi energi mekanis menjadi energi listrik. Dikarenakan energi listrik dibutuhan setiap waktu, sehingga membuat generator bekerja secara terus-menerus yang mengakibatkan timbulnya rugi daya, salah satunya rugi daya stator. Rugi daya stator akan membuat temperatur pada stator tersebut akan semakin tinggi, sehingga dibutuhkan sistem pendingin yaitu generator stator cooling water(GSCW). Sistem pendingin tersebut akan menjaga temperatur stator tetap dalam standarnya, sehingga generator dapat bekerja secara efisien. Berdasarkan dari hasil penelitian generator unit 1 PLTU Lontar. Diperoleh pada beban minimum yang terdapat pada pukul 03:00 dengan daya aktif sebesar 171,87 MW memiliki rugi daya stator sebesar 178,67 kW dan efektivitas pendingin air sebesar 93,51 % dengan temperatur actual 44,58 C° dan temperatur perhitungan 41,69 C°. Pada beban maksimum yang terdapat pada pukul 12:00 dengan daya aktif sebesar 292,73 MW memiliki rugi daya stator sebesar 430,12 kW dan efektivitas pendingin air sebesar 97,90 % dengan temperatur actual 51,95 C° dan temperatur perhitungan 50,86 C°.
In everyday life, electricity is a major need that is widely needed and utilized by humans. Electrical energy is produced by a device called a generator, where the generator is a synchronous machine that converts mechanical energy into electrical energy. Because electrical energy is needed all the time, making the generator work continuously results in power losses, one of which is the loss of stator power. Stator power loss will make the temperature in the stator higher, so a cooling system is needed, namely the generator stator cooling water (GSCW). The cooling system will keep the stator temperature within its standard so that the generator can work efficiently. Based on the results of the research, generator unit 1 PLTU Lontar. obtained at a minimum load of 03:00 with an active power of 171.87 MW, a stator power loss of 178.67 kW, and a water cooling effectiveness of 93.51% at 44.58 ° and a calculation temperature of 41.69 ° At the maximum load at 12:00 with an active power of 292.73 MW, the stator power loss is 430.12 kW and the water cooling effectiveness is 97.90% with an actual temperature of 51.95 C° and a calculation temperature of 50.86 C°.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Rugi-rugi daya, Temperatur, Sistem pendingin air Power Losses, Temperature, System Cooling Water |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 21 Oct 2025 08:51 |
| Last Modified: | 21 Oct 2025 08:51 |
| URI: | https://repository.itpln.ac.id/id/eprint/2719 |