Safitri, Zulhanifah Nur Ari and handayani, oktaria (2022) ANALISIS SUSUT UMUR BERDASARKAN PEMBEBANAN PADA TRANSFORMATOR DAYA 329 MVA BLOK 3 PLTGU PRIOK. Diploma thesis, ITPLN.
SKRIPSI 201811108 ZULHANIFAH NUR ARI SAFITRI.pdf
Restricted to Registered users only
Download (3MB)
Abstract
Transformator Daya pada sistem pembangkitan listrik merupakan salah satu komponen utama yang berfungsi untuk menyalurkan daya dari generator yang bertegangan menengah ke transmisi yang bertegangan tinggi. Berdasarkan IEC umur dasar dari suatu transformator adalah 20,55 tahun, akan tetapi tidak semua transformator dapat beroperasi sesuai ketentuan standar. Transformator Daya PLTGU Priok Blok 3 ini sudah beroperasi selama 10 tahun dengan pola pembebanan tidak pernah lebih dari 80%. Pada penelitian ini akan menganalisa bagaimana pengaruh pembebanan terhadap susut umur dan mengetahui sisa umur transformator dengan sampel pembebanan harian selama 1 bulan yaitu pada bulan Februari 2022 serta menggunakan data spesifikasi trafo dan suhu ambient yaitu 31oC yang didapat dari wawancara, observasi dan studi kepustakaan. Berdasarkan hasil perhitungan diketahui bahwa pembebanan berbanding lurus dengan susut umur transformator dan pada Transformator Blok 3 PLTGU Priok mengalami susut umur sebesar 3,1% dengan sisa umur transformator yaitu 10,2 Tahun. Dari studi kasus diatas maka kita dapat menganalisis faktor apa saja yang lebih dominan terhadap umur trafo sehingga bisa dijadikan referensi untuk pengoperasian transformator yang lebih aman sehingga life time trafo dapat terjaga.
The power transformer in the power generation system is one of the main components that functions to transfer power from a medium-voltage generator to a high-voltage transmission. According to IEC the basic life of a transformer is 20.55 years, but not all transformers can operate according to the standard requirements. The Priok Block 3 PLTGU Power Transformer has been operating for 10 years with a loading pattern of never more than 80%. This study will analyze how the effect of loading on life loss and find out the remaining life of the transformer with a sample of daily loading for 1 month, namely in February 2022 and using transformer specification data and ambient temperature of 31oC obtained from interviews, observations and literature studies. Based on the calculation, it is known that the loading is directly proportional to the life loss of the transformer and the Transformer Block 3 PLTGU Priok experiences a life loss of 3.1% with the remaining life of the transformer, which is 10.2 years. From the case study above, we can analyze which factors are more dominant than the age of the transformer so that it can be used as a reference for safer transformer operation so that the transformer's lifetime can be maintained.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Susut Umur, Sisa Umur dan IEC Life Loss, Remaining Life and IEC |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 22 Oct 2025 02:46 |
| Last Modified: | 22 Oct 2025 02:46 |
| URI: | https://repository.itpln.ac.id/id/eprint/2726 |