Wulandari, Rizka Afrita Sri and Samsurizal, Samsurizal (2022) ANALISIS KETIDAKSEIMBANGAN BEBAN TERHADAP RUGI ARUS NETRAL DAN KEANDALAN TRANSFORMATOR DISTRIBUSI 400 kV PADA GARDU DISTRIBUSI MJL. Diploma thesis, ITPLN.
SKRIPSI 201811116 RIZKA AFRITA SRI WULANDARI.pdf
Restricted to Registered users only
Download (4MB)
Abstract
Ketidakseimbangan beban terjadi dikarenakan besarnya beban pada tiap fasa berbeda. Yang mana hal ini mengakibatkan adanya arus yang mengalir pada penghantar netral yang menimbulkan terjadinya rugi arus netral, serta kerugian berupa daya yang hilang dan kerugian materi. Pada saat dilakukan pencatatan beban pada gardu distribusi MJL, besarnya nilai beban pada tiap-tiap fasanya berbeda. Yang mana hal ini menyebabkan terjadinya rugi arus netral sebesar 2,03 kW dengan besarnya daya yang hilang sebesar 240844,2367 kW dan kerugian materi sebesar Rp 347.947.668,8. Untuk mengatasi hal tersebut, maka perlu dilakukan pemerataan beban dengan menggunakan metode pecah beban. Metode pecah beban dilakukan dengan cara memindahkan beban pada fasa yang tinggi ke fasa yang memiliki beban lebih rendah. Setelah dilakukan pemerataan beban, besarnya rugi arus netral turun menjadi 0,003 kW dengan besarnya daya yang hilang sebesar 45793,79 kW dan kerugian materi sebesar Rp 66.158.285,43. Sehingga diketahui bahwa ketidakseimbangan beban memberikan pengaruh terhadap besarnya rugi arus netral serta kerugian berupa daya yang hilang dan kerugian materi.
Load imbalance happened because the amount of load in each phase is different. Which is what this results in a current flowing at a neutral conductor what causes it to happen a neutral current loss, as well as losses in the form of lost power and material losses. When recording the load at the MJL distribution substation, the amount of load value in each phase is different. Which this caused a neutral current loss of 2.03 kW with a loss of power loss of 240844.2367 kW and a material loss of Rp 347,947,668.8. To overcome this, it is necessary to equalize the load using the load rupture method. The load rupture method is carried out by moving the load on a high phase to a phase that has a lower load. After load equalization, the amount of neutral current loss decreased to 0.003 kW with the amount of power lost by 45793.79 kW and material loss of Rp 66,158,285.43. So it is known that the load imbalance has an influence on the amount of neutral current loss and losses in the form of lost power and material losses.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Ketidakseimbangan Beban, Rugi Arus Netral, Daya yang Hilang Load Imbalance, Neutral Current Losess, Power Losses |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 22 Oct 2025 03:05 |
| Last Modified: | 22 Oct 2025 03:05 |
| URI: | https://repository.itpln.ac.id/id/eprint/2730 |