Wijayanto, Afrian Tri and Rahayu, Sofitri (2022) PERBANDINGAN PENGGUN AAN STATIC VAR COMnENSATOR (SVC) DAN KAPASITOR BANK TERHADAP ALIRAN DAYA DAN PROFIL TEGANGAN MENGGUNAKAN SOFTWARE ETAP 16. Diploma thesis, ITPLN.
SKRIPSI 201811141 AFRIAN TRI WIJAYANTO.pdf
Restricted to Registered users only
Download (5MB)
Abstract
Terjadinya penurunan kualitas energi listrik menyebabkan kerugian dua pihak antara perusahaan dan konsumen, oleh karena itu harus ada tindakan yang dilakukan pada jaringan transmisi untuk meningkatkan kualitas energi listrik yaitu dengan cara mengkompensasi daya reaktif pada jaringan transmisi dengan menggunakan SVC (Static Var Compensator) dan Kapasitor Bank. SVC (Static Var Compensator) merupakan salah satu peralatan FACTS (Flexible Alternating Current Transmission Systems) berguna untuk mengoptimalkan stabilitas tegangan dan mengoptimalkan kemampuan pada transfer daya pada jaringan transmisi. Disini penulis melakukan penelitian untuk mengetahui tentang pengaruh pemasangan SVC dan Kapasitor Bank terhadap aliran daya dan tegangan pada Subsistem melalui simulai ETAP 16. Dari hasil simulai dengan memasang SVC dan Kapasitor Bank pada Bus Maximangando dengan kapasitar Qc 25 MVAR didapatkan hasil peningkatan nilai tegangan rata-rata setiap bus gardu induk Subsistem sebesar 0,710 kV dan 0,875 kV. Peningkatan transfer daya aktif setiap bus gardu induk Subsistem meningkat dengan total peningkatan mencapai 7,704 MW dan 9,271 MW.
The decline in the quality of electrical energy causes losses for both parties between the company and consumers, therefore there must be action taken on the transmission network to improve the quality of electrical energy, namely by compensating for reactive power in the transmission network using SVC (Static Var Compensator) and Capacitor Bank . SVC (Static Var Compensator) is one of the FACTS (Flexible Alternating Current Transmission Systems) equipment that is useful for optimizing the ability to repair and optimize the ability to transfer power on the transmission network. Here the author conducts research to find out about the effect of installing SVC and Capacitor Bank on the flow of power and voltage in the Subsystem through the ETAP 16 simulation. From the simulation results by installing SVC and Capacitor Bank on Maximangando Bus with a Qc 25 MVAR capacitance, the results show an increase in the average voltage value. each substation bus Subsystem of 0,710 kV and 0,875 kV. The increase in active power transfer for each subsystem substation bus increased with a total increase of 7,704 MW and 9,271 MW
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | SVC, Kapasitor Bank, Tegangan, Daya, Subsistem SVC, Capacitor Bank, connection, Power, Subsystem |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 22 Oct 2025 07:06 |
| Last Modified: | 22 Oct 2025 07:06 |
| URI: | https://repository.itpln.ac.id/id/eprint/2762 |