Perdana, Ade Rachman and Hariyanto, Agung (2022) ANALISIS PENGARUH KETIDAKSEIMBANGAN BEBAN TERHADAP EFISIENSI PADA TRANSFORMATOR DISTRIBUSI GARDU RBC-074 PT. PLN (PERSERO) ULP BINTAN CENTER. Diploma thesis, ITPLN.
SKRIPSI 201811038 ADE RACHMAN PERDANA.pdf
Restricted to Registered users only
Download (3MB)
Abstract
Disaat pendistribusian tenaga listrik, meski beban pada transformator diupayakan seimbang pada masing-masing fasanya terdapat arus yang sama besar, akan tetapi ketidakseimbangan beban mungkin akan terjadi. Hal ini disebabkan waktu pemakain beban yang tidak bersamaan yang menyebabkan antar fasa mengalami nilai pembebanan yang berbeda-beda. Pengaruh dari ketidakseimbangan beban membuat rugi-rugi akibat arus netral pada penghantar netral serta yang menuju ke tanah menjadi besar. Efek nya akan menyebabkan nilai efisiensi pada suatu transformator menjadi menurun mengakibatkan umur pemakaian suatu transformator menjadi berkurang. Selain itu kualias dalam menyalurankan energi listrik terjadi penurunan. Berdasarkan pada hasil penelitian yang telah di analisis menggunakan perhitungan manual di peroleh bahwa ketidakseimbangan beban pada saat WBP lebih tinggi terjadi di malam hari. dimana pada tanggal 19-03-2022 pukul 18:00 WIB di peroleh nilai persentase ketidakseimbangan beban tertinggi pada Transformator Gardu RBC-074 sebesar 26.533% beserta nilai persentase efisiensi transformator terendah sebesar 86.671%. Sedangkan untuk nilai rugi arus netral pada penghantar netral maupun yang mengalir ke tanah mencapai 4.148% dan 9.179% yang merupakan nilai tertinggi. Sedangkan untuk nilai persentase ketidakseimbangan terendah pada tanggal 16-03-2022 pukul 09:00 WIB sebesar 18.966%.
When distributing electric power, even though the load on the transformer is attempted to be balanced in each phase there is an equal current, but an imbalance in the load may occur. This is due to the time when the load is not used simultaneously which causes the phases to experience different loading values. The influence of the load imbalance makes losses due to neutral current in the neutral conductor and towards the ground being large. The effect will cause the efficiency value of a transformer to decrease resulting in a reduced service life of a transformer. In addition, the quality in distributing electrical energy has decreased. Based on the results of research that has been analyzed using manual calculations, it is found that the load imbalance when the WBP is higher occurs at night. where on 19-03-2022 at 18:00 WIB the highest percentage value of load imbalance was obtained at the RBC-074 Substation Transformer of 26.533% along with the lowest percentage value of transformer efficiency of 86.671%. As for the value of the loss of neutral current in the neutral conductor and that flows to the ground, it reaches 4.148% and 9.179%, which are the highest values. As for the lowest percentage value of imbalance on 16-03-2022 at 09:00 WIB, it is 18.966%.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Ketidakseimbangan beban, Efisiensi, Rugi-rugi, Transformator Unbalance load, Efficiency, losses, Transformer |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 23 Oct 2025 03:11 |
| Last Modified: | 23 Oct 2025 03:11 |
| URI: | https://repository.itpln.ac.id/id/eprint/2801 |