Abstract

Pemasangan trafo sisipan menjadi metode efektif dalam mengatasi beban berlebih pada trafo distribusi. Trafo sisipan berfungsi sebagai transformator tambahan yang membagi beban, khususnya saat trafo distribusi mengalami keadaan Overload. Penelitian ini mengfokuskan pada trafo distribusi LSA 172 Sp. 4 di Kampung Jawa. Melalui perhitungan manual sebelum pemasangan trafo sisipan, ditemukan pembebanan sebesar 91%. Setelah pemasangan trafo sisipan, nilai pembebanan turun menjadi 53%, mengindikasikan penurunan beban sebesar 38%. Hasil simulasi dengan aplikasi ETAP juga menunjukkan penurunan pembebanan dari 93,2% menjadi 53,7%, menandakan penurunan beban sebesar 39,5%. Kombinasi perhitungan manual dan simulasi memberikan gambaran komprehensif tentang efektivitas pemasangan trafo sisipan dalam mengoptimalkan kinerja trafo distribusi dan mengurangi beban berlebih. Hasil dari simulasi menunjukkan bahwa pemasangan trafo sisip berhasil meningkatkan nilai Drop Voltage dari 96,15% menjadi 97,64%. Hal ini mengindikasikan peningkatan tegangan sebesar 6 volt, dari 385 volt menjadi 391 volt, setelah pemasangan trafo sisip. Temuan ini menegaskan bahwa trafo sisip tidak hanya berperan sebagai pemecah beban, tetapi juga efektif dalam meminimalisir Drop Voltage atau meningkatkan nilai tegangan pada trafo distribusi LSA 172 yang mengalami Overload.

The installation of an insertion transformer proves to be an effective method in addressing excessive loads on distribution transformers. The insertion transformer functions as an additional transformer that shares the load, particularly when the distribution transformer experiences Overload conditions. This study focuses on distribution transformer LSA 172 Sp. 4 in Kampung Jawa. Through manual calculations before the installation of the insertion transformer, a load of 91% was determined. After the installation of the insertion transformer, the load value decreased to 53%, indicating a reduction in load of 38%. Simulation results using the ETAP application also showed a decrease in the load from 93,2% to 53,7%, indicating a reduction in load of 39.5%. The combination of manual calculations and simulations provides a comprehensive overview of the effectiveness of installing an insertion transformer in optimizing the performance of distribution transformers and reducing excessive loads. The simulation results indicate a decrease in voltage drop. The simulation results demonstrate that the installation of the insertion transformer successfully increased the voltage drop value from 96.15% to 97.64%. This indicates an increase in voltage of 6 volts, from 385 volts to 391 volts, after the installation of the insertion transformer. These findings confirm that the insertion transformer not only serves as a load breaker but is also effective in minimizing voltage drop or increasing voltage values in distribution transformer LSA 172 experiencing Overload conditions.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Trafo Distribusi, Trafo Sisip, Overload, Drop Voltage Distribution Transformer, Insert Transformer, Overload, Drop Voltage
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 24 Oct 2025 07:13
Last Modified: 24 Oct 2025 07:13
URI: https://repository.itpln.ac.id/id/eprint/2922

Actions (login required)

View Item
View Item