Penelitian ini bertujuan untuk menganalisis kinerja sistem Uninterruptible Power Supply (UPS) dalam menghadapi pembebanan di PT PLN Nusantara Power Unit Pembangkit Pembangkit Listrik Tenaga Gas Uap (PLTGU) Gresik. Semua system AC dan DC akan disuplai oleh baterai berkapasitas 1200 AH. Beban yang harus utamanya adalah Personal Computer Constant Current Regulator (CCR) dan Personal Computer Direct Digital Controller (DDC) dan sistem Inverter UPS ini akan mensuplai daya listrik sebesar 5765 watt Ketika unit pembangkit ST1 mengalami blackout. Tingkat penurunan daya inverter dari tahun 2021 ke tahun 2022 sebesar 0,26%. Kemudian pada tahun 2022 hingga 2023 terjadi penurunan daya inverter sebesar 0,41%. Ini menunjukkan penurunan total daya inverter UPS sebesar 0,67% dari tahun 2021 hingga 2023. Pada pengukuran nilai tegangan pengisian baterai pada UPS dan hasil perawatan baterai pada bulan September 227.37 volt, kemudian pada pengukuran nilai tegangan pengisian baterai pada bulan Oktober 227,35 volt, kemudian pada pengukuran nilai tegangan pengisian baterai pada bulan November 227,41 volt. Pengukuran tegangan baterai pada UPS pada bulan September hingga November menunjukkan perbandingan menunjukkan bahwa kondisi baterai UPS tetap baik dan dapat diandalkan untuk menyediakan daya cadangan yang diperlukan dalam situasi darurat atau pemadaman Listrik.

This research aims to analyze the performance of the Uninterruptible Power Supply (UPS) system in dealing with loading at PT PLN Nusantara Power Unit, Steam Gas Power Plant (PLTGU) Gresik. All AC and DC systems will be supplied by a 1200 AH capacity battery. The main load must be the Personal Computer Constant Current Regulator (CCR) and Personal Computer Direct Digital Controller (DDC) and this UPS Inverter system will supply 5765 Watt of electrical power when the ST1 generating unit experiences a blackout. The rate of decline in inverter power from 2021 to 2022 is 0.26%. Then from 2022 to 2023 there will be a decrease in inverter power of 0.41%. This shows a decrease in total UPS inverter power of 0.67% from 2021 to 2023. When measuring the battery charging voltage value on the UPS and battery maintenance results in September it was 227.37 volts, then when measuring the battery charging voltage value in October it was 227.35 volts , then when measuring the battery charging voltage value in November it was 227.41 volts. Measuring battery voltage on the UPS from September to November shows that the UPS battery condition remains good and can be relied upon to provide backup power needed in emergency situations or power outages.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: UPS, Power Supply,Energi Listrik UPS, Power Supply, Electrical energy
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 24 Oct 2025 08:02
Last Modified: 24 Oct 2025 08:02
URI: https://repository.itpln.ac.id/id/eprint/2937

Actions (login required)

View Item
View Item