ANALISIS PENGARUH KADAR AIR TERHADAP TEGANGAN TEMBUS PADA MINYAK TRANSFORMATOR DI GIS 150 kV DENGAN METODE KORELASI

Silalahi, Monalisa Maudy Deniro and Abduh, Syamsir (2024) ANALISIS PENGARUH KADAR AIR TERHADAP TEGANGAN TEMBUS PADA MINYAK TRANSFORMATOR DI GIS 150 kV DENGAN METODE KORELASI. Diploma thesis, ITPLN.

[thumbnail of SKRIPSI 202011269 MONALISA MAUDY DENIRO SILALAHI.pdf] Text
SKRIPSI 202011269 MONALISA MAUDY DENIRO SILALAHI.pdf
Restricted to Registered users only

Download (6MB)

Abstract

Dalam pengoperasiannya, minyak transformator sebagai media isolasi dan pendingin dapat mengalami kegagalan isolasi. Kegagalan isolasi pada transformator dapat terjadi karena peningkatan kontaminan pada minyak transformator salah satunya adalah kontaminan air. Penelitian ini bertujuan untuk mengetahui bagaimana pengaruh kadar air terhadap tegangan tembus minyak transformator. Dengan menggunakan metode kuantitatif, pengujian ini dilakukan dengan menggunakan standar IEC 60422 2013. Hasil dari pengujian ini menunjukkan semakin besar nilai kadar air yang terkandung di dalam minyak transformator maka semakin kecil nilai tegangan tembus minyak transformator tersebut. Kadar air yang tinggi dalam minyak dapat dikurangi dengan melakukan filtrasi pada minyak tersebut. Dari hasil pengujian tegangan tembus minyak transformator #1 dan minyak transformator #2 menunjukkan bahwa kadar air memberikan pengaruh sebesar 98,96% terhadap tegangan tembus minyak transformator #1 dan sebesar 41,34% terhadap tegangan tembus minyak transformator #2. Sehingga dapat disimpulkan bahwa semakin besar nilai kontaminan air yang terkandung di dalam minyak transformator maka semakin kecil nilai tegangan tembusnya.

In operation, transformer oil as an insulating and cooling medium can experience insulation failure. Insulation failure in a transformer can occur due to an increase in contaminants in the transformer oil, one of which is water contaminants. This research aims to determine how water content influences the breakdown voltage of transformer oil. Using quantitative methods, this test was carried out using the IEC 60422 2013 standard. The results of this test show that the greater the value of the water content contained in the transformer oil, the smaller the breakdown voltage value of the transformer oil. High water content in oil can be reduced by filtrating the oil. From the results of testing the breakdown voltage of transformer oil #1 and transformer oil #2, it shows that water content has an influence of 98,96% on the breakdown voltage of transformer oil #1 and 41,34% on the breakdown voltage of transformer oil #2. So it can be concluded that the greater the value of water contaminants contained in transformer oil, the smaller the breakdown voltage value.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: tegangan tembus, kontaminan air, minyak transformator, kegagalan isolasi, isolasi. breakdown voltage, water contaminants, transformer oil, insulation failure, insulation
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro