ANALISIS UNJUK KERJA CAPACITIVE VOLTAGE TRANSFORMER PADA GARDU INDUK 150 KV PONDOK KELAPA DI PT PLN (PERSERO) CAWANG

Sandiyudha, Asprinda Al Akbar and Pasra, Nurmiati (2024) ANALISIS UNJUK KERJA CAPACITIVE VOLTAGE TRANSFORMER PADA GARDU INDUK 150 KV PONDOK KELAPA DI PT PLN (PERSERO) CAWANG. Diploma thesis, ITPLN.

[thumbnail of SKRIPSI 202011274 ASPRINDA AL AKBAR SANDIYUDH.pdf] Text
SKRIPSI 202011274 ASPRINDA AL AKBAR SANDIYUDH.pdf
Restricted to Registered users only

Download (8MB)

Abstract

Capacitive Voltage Transformer (CVT) adalah peralatan yang mentransformasi tegangan tinggi ke tegangan lebih rendah untuk kebutuhan peralatan proteksi, sehingga pentingnya menjaga kinerja CVT. Pada Gardu Induk Pondok Kelapa terjadi gangguan pada CVT dan telah diketahui penyebabnya, yaitu isolasi yang buruk sehingga terjadi overheat dan mengakibatkan CVT terbakar. Sehingga, dilakukan penggantian dan peneliti ingin mengetahui perubahan kondisi sebelum dan sesudah penggantian serta mengetahui kondisi pada CVT yang dilakukan penggantian ketika terjadi undervoltage dengan mensimulasikan ETAP. Hasil dari penelitian ini, pada pengujian tan delta Bay Jatirangon tahun 2023 memiliki nilai yang terburuk dibandingkan dengan tahun sebelumnya, yaitu fasa R 1,3626%, fasa S 1,3567%, fasa T 1,3741%, nilai tersebut tidak memenuhi standar SKDIR0520K/DIR/2014, yaitu

Capacitive Voltage Transformer (CVT) is equipment that transforms high voltage to lower voltage for protection equipment needs, so it is important to maintain CVT performance. At the Pondok Kelapa substation there was a problem with the CVT and the cause was known, namely poor insulation which resulted in overheating and causing the CVT to catch fire. So, a replacement was carried out and the researchers wanted to know the changes in conditions before and after the replacement and to know the condition of the CVT that was replaced when undervoltage occurred by simulating ETAP. The results of this research, in the 2023 Bay Jatirangon tan delta test, had the worst values compared to the previous year, namely R phase 1.3626%, S phase 1.3567%, T phase 1.3741%, these values do not meet the SKDIR0520K standard /DIR/2014, namely

Item Type: Thesis (Diploma)
Uncontrolled Keywords: CVT, Tahanan Isolasi, Tan Delta, Tahanan Pentanahan, Undervoltage CVT, Insulation Resistance, Tan Delta, Grounding Resistance, Undervoltage
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 28 Oct 2025 04:49
Last Modified: 28 Oct 2025 04:49
URI: https://repository.itpln.ac.id/id/eprint/3037

Actions (login required)

View Item
View Item