Abstract

Lightning Arrester (LA) adalah perangkat yang dirancang untuk melindungi peralatan listrik dari lonjakan tegangan yang disebabkan oleh surja hubung atau surja petir. Penelitian ini memiliki tujuan untuk mengetahui kinerja lightning arrester dengan pengujian arus bocor dan tahanan isolasi, juga untuk melihat perkiraan besarnya arus bocor dan tahanan isolasi saat peralatan berusia hingga 20 tahun. Arus bocor adalah arus yang mengalir melalui isolasi suatu sistem tenaga listrik, dan merupakan ukuran kemampuan isolasi untuk menahan tekanan tegangan. Tahanan isolasi merupakan keadaan di mana suatu peralatan memiliki nilai resistansi terhadap tegangan untuk mencegah terjadinya korsleting atau kerusakan lainnya. Metode yang digunakan pada penelitian ini yaitu metode deskriptif kuantitatif. Dimana subjek penelitian yang akan diteliti yaitu arus bocor dan tahanan isolasi yang pengujiannya dilakukan selama 3 tahun terakhir. Hal tersebut dilakukan untuk mengetahui layak atau tidaknya lightning arrester yang sudah berusia lebih dari 10 tahun. Pengukuran dilakukan dengan menggunakan alat Leakage Current Measurement (LCM) dan Megger Kyoritsu tipe 3125 dengan injeksi tegangan 5kV. Untuk injeksi tegangan 5000v (5kV), nilai maksimal alat uji sebesar >1000GΩ. Standar yang digunakan yaitu >1kV/1MΩ. Hasil penelitian menunjukkan bahwa lightning arrester masih layak beroperasi berdasarkan pengujian arus bocor dan tahanan isolasi. Perkiraan arus bocor dan tahanan isolasi selama tujuh tahun ke depan menghasilkan nilai uji yang bervariasi. Dapat disimpulkan bahwa semakin besar arus bocor, kinerja LA semakin menurun, dan semakin kecil tahanan isolasi, kinerja LA juga menurun.

Lightning Arrester (LA) is a device designed to protect electrical equipment from voltage spikes caused by surges or lightning surges. This study aims to determine the performance of lightning arresters by testing leakage current and insulation resistance, as well as to see the predicted amount of leakage current and insulation resistance when the equipment is up to 20 years old. Leakage current is the current flowing through the insulation of an electric power system, and is a measure of the ability of the insulation to withstand voltage stress. Insulation resistance is a state in which an equipment has a resistance value to voltage to prevent short circuits or other damage. The method used in this research is quantitative descriptive method. Where the subject of research to be studied is leakage current and insulation resistance whose testing has been carried out for the last 3 years. This is done to determine whether or not the lightning arrester is more than 10 years old. Measurements were made using the Leakage Current Measurement (LCM) tool and Megger Kyoritsu type 3125 with a voltage injection of 5kV. For 5000v (5kV) voltage injection, the maximum value of the test tool is >1000GΩ. The standard used is >1kV/1MΩ. The results showed that the lightning arrester is still feasible to operate based on leakage current and insulation resistance testing. Estimated leakage current and insulation resistance for the next seven years

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Lightning Arrester, Arus Bocor, Tahanan Isolasi Lightning Arrester, Leakage Current, Insulation Resistance
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Depositing User: Sudarman
Date Deposited: 28 Oct 2025 06:26
Last Modified: 28 Oct 2025 06:26
URI: https://repository.itpln.ac.id/id/eprint/3040

Actions (login required)

View Item
View Item