ANALISA KONDISI GIS BERDASARKAN PENGUJIAN PARTIAL DISCHARGE, TITIK EMBUN DAN NILAI KELEMBABAN GAS SF6 PADA GIS 150kV DAAN MOGOT

Sibuea, Terry Dodo and Sirait, Rummi (2024) ANALISA KONDISI GIS BERDASARKAN PENGUJIAN PARTIAL DISCHARGE, TITIK EMBUN DAN NILAI KELEMBABAN GAS SF6 PADA GIS 150kV DAAN MOGOT. Diploma thesis, ITPLN.

[thumbnail of SKRIPSI 202011345 TERRY DODO SIBUEA.pdf] Text
SKRIPSI 202011345 TERRY DODO SIBUEA.pdf
Restricted to Registered users only

Download (5MB)

Abstract

Pada sistem tenaga listrik, kualitas dari suatu bahan isolasi merupakan hal yang sangat penting dan harus diperhatikan demi menjaga kinerja dari peralatan listrik, sehingga dibutuhkan pemeliharaan agar menjaga alat alat peralatan listrik tetap bagus. Salah satu isolasi yang menjaga alat alat agar tetap aman yaitu Gas SF6 yang berada pada GIS atau Gas Insulated Switchgear . Dengan menggunakan alat SF6 Multi Analyzer sebagai alat untuk menguji Gas SF6 maka akan di dapatkan hasil yang maksimal dan akan di analisis pada penelitian ini. Penelitian ini bertujuan untuk menganalisis Dew Point (titik embun) dan juga Moisture Content (kelembaban). Hasil dari penelitian ini menunjukkan Gas SF6 pada GIS Daan Mogot ini masih tergolong bagus karena Dew Point nya masih memenuhi standar, begitu juga dengan kelembabannya berada di bawah 500 PPMV . Korelasi Dew Point dengan Moisture Content mendapatkan nilai r yaitu 0.472. Nilai ini menunjukkan kedua variable tersebut memiliki korelasi yang lemah dan bentuk hubungannya adalah linear positif . Korelasi antara Purity dengan Dew Point adalah -0.05 atau memiliki korelasi yang lemah dan juga hasilnya menunjukkan bahwa nilainya linear negatif atau dapat dikatakan berbanding terbalik.

In an electric power system, the quality of an insulation material is very important and must be considered in order to maintain the performance of electrical equipment, so maintenance is needed to keep electrical equipment good. One of the insulation that keeps tools safe is SF6 Gas which is in GIS or Gas Insulated Switchgear. By using the SF6 Multi Analyzer tool as a tool to test SF6 Gas, maximum results will be obtained and will be analyzed in this study. This study aims to analyze the Dew Point and also the Moisture Content. The results of this study show that the SF6 gas in the Daan Mogot GIS is still relatively good because the Dew Point still meets the standard, as well as the humidity is below 500 PPMV. The correlation of Dew Point with Moisture Content gets an r value of 0.472. This value shows that the two variables have a weak correlation and the form of the relationship is linear positive. The correlation between Purity and Dew Point is -0.05 or has a weak correlation and also the results show that the value is linear negative or can be said to be inversely proportional.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: SF6 , GIS , Dew Point dan Moisture Content. SF6 ,GIS , Dew Point And Moisture Content
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 28 Oct 2025 06:43
Last Modified: 28 Oct 2025 06:43
URI: https://repository.itpln.ac.id/id/eprint/3045