Gardu induk 150 kV merupakan komponen penting dalam sistem tenaga listrik yang berperan dalam menjaga stabilitas dan keandalan pasokan listrik. Salah satu tantangan utama dalam operasi gardu induk adalah menangani arus gangguan yang dapat menyebabkan risiko bahaya bagi manusia dan peralatan di sekitarnya. Untuk mengatasi hal ini, diperlukan sistem pembumian yang kuat sesuai dengan standar keselamatan. Penelitian ini bertujuan untuk merancang sistem pembumian yang aman dan efektif untuk Gardu Induk 150 kV dengan menggunakan standar IEEE 80-2000. Pada Gardu Induk 150 kV terdapat bahwa tegangan mesh sebesar sebesar 423,9 Volt dimana nilainya lebih rendah daripada tegangan sentuh yang diizinkan yaitu 820,7 Volt dan tegangan langkah maksimum nya sebesar 432,24Volt lebih kecil daripada tegangan langkah yang dihasilkan berada di bawah batas yang diizinkan, menjadikan desain sistem pembumian ini aman dan sesuai standar. Konstruksi grid-rod dengan jarak antar grid 4 meter terbukti lebih baik. Desain yang dihasilkan memenuhi standar IEEE, memastikan keamanan dan keandalan operasional gardu induk.

The 150 kV substation is a critical component in the electrical power system, playing a key role in maintaining the stability and reliability of electricity supply. A major challenge in substation operation is handling fault currents that pose risks to both personnel and nearby equipment. To address this, a robust grounding system compliant with safety standards is required. This study aims to design a safe and effective grounding system for the 150 kV Substation using IEEE 80-2000 standards. At the 150 kV Substation, the mesh Voltage is measured at 423.9 Volts, which is lower than the allowable touch Voltage of 820.7 Volts, and the maximum step Voltage is 432.24 Volts, well below the permissible limit. This indicates that the grounding system design is safe and meets the standards. Additionally, the grid-rod construction with a 4-meter grid spacing proves to be more effective. The resulting design meets IEEE standards, ensuring the safety and operational reliability of the substation.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Sistem Pembumian, IEEE Std 80-2000, Tegangan Sentuh, Tegangan Langkah,grid-rod. grounding system, fault current, touch Voltage, step Voltage, IEEE 80-2000, grid-rod.
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 28 Oct 2025 08:06
Last Modified: 28 Oct 2025 08:06
URI: https://repository.itpln.ac.id/id/eprint/3066

Actions (login required)

View Item
View Item