Parhusip, Antonius and Hasanah, Aas Wasri (2024) ANALISIS PARTIAL DISCHARGE PADA KUBIKEL INCOMING 20 kV DENGAN METODE ULTRA TEV PLUS DI GARDU INDUK CIKUPA. Diploma thesis, ITPLN.
SKRIPSI 202011216 ANTONIUS PARHUSIP.pdf
Restricted to Registered users only
Download (5MB)
Abstract
Penelitian ini dilakukan di PT. PLN (Persero) Unit Layanan Gardu Induk Cikupa dengan tujuan dari penelitian ini adalah untuk melakukan analisis penyebab dan penilaian terhadap aktivitas partial discharge guna menjaga keandalan dan keamanan sistem kelistrikan. Aktivitas partial discharge yang terdeteksi pada kabel inti 1 sebesar 31 dB yang disebabkan oleh karna sambungan kurang ketat yang memberikan ruang dan menimbulkan aktivitas PD dan interpretasinya kemungkinan PD tingkat menengah. Pada kabel inti 1 sebesar 29 dB yang disebabkan oleh adanya kelembaban pada peralatan dan interpretasinya kemungkinan PD tingkat rendah. Pada kabel inti 3 sebesar 30 dB yang disebabkan oleh karna sambungan kurang ketat dan interpretasinya kemungkinan PD tingkat menengah. Pada titik kabel inti 4 sebesar 30 yang disebabkan oleh karna sambungan kurang ketat dan interpretasinya kemungkinan PD tingkat menengah. Pada titik kabel inti 5 sebesar 37 dB yang disebabkan oleh sambungan yang kurang ketat dan interpretasinya kemungkinan logam mengambang/koneksi jelek. Pada pengujian kabel box sebesar 11dB yang artinya dalam kondisi normal.
This research was conducted at PT. PLN (Persero) Cikupa Substation Service Unit with the aim of analyzing the causes and assessing partial discharge activities to maintain the reliability and safety of the electrical system. Partial discharge activity detected on core cable 1 was 31 dB, caused by a loose connection that created space and triggered PD activity, with an interpretation indicating a medium-level PD. For core cable 1, the detected level was 29 dB, caused by moisture in the equipment, interpreted as low-level PD. Core cable 3 showed 30 dB, caused by a loose connection, interpreted as medium-level PD. At the point of core cable 4, the detected level was 30 dB, caused by a loose connection, interpreted as medium-level PD. For core cable 5, the detected level was 37 dB, caused by a loose connection, interpreted as floating metal/poor connection. The cable box test showed 11 dB, indicating normal conditions.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Partial discharge, kubikel incoming 20 kV, Ultra TEV Plus. Partial discharge, incoming cubicle 20 kV |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 29 Oct 2025 03:14 |
| Last Modified: | 29 Oct 2025 03:14 |
| URI: | https://repository.itpln.ac.id/id/eprint/3093 |