Study of Losses in the Low Voltage Network of the 620.CR Distribution Substation at PT.PLN (Persero) ULP Makale

Tandiopang, Yehezkiel and Hidayat, Syarif (2024) Study of Losses in the Low Voltage Network of the 620.CR Distribution Substation at PT.PLN (Persero) ULP Makale. Diploma thesis, ITPLN.

[thumbnail of SKRIPSI 202011220 YEHEZKIEL TANDIOPANG.pdf] Text
SKRIPSI 202011220 YEHEZKIEL TANDIOPANG.pdf
Restricted to Registered users only

Download (4MB)

Abstract

Salah satu permasalahan yang sering terjadi pada jaringan distribusi PT.PLN (Persero) adalah rugi-rugi daya, adapun penyebab rugi-rugi daya anatara lain adalah adanya ketidakseimbangan beban antara fasa, faktor daya yang rendah, panjang jaringan dan lain sebagainya. Dalam penelitian ini, dilakukan analisis perhitungan jaringan tegangan rendah dengan menghitung rugi daya relatifnya. Hal ini dilakukan dengan menghitung jatuh tegangan, tahanan saluran, rugi daya rata-rata, daya tersalur, sehingga diperoleh rugi daya relatifnya. Saat siang hari, rugi daya relatif gardu distribusi 620.CR adalah 2,92%, sedangkan pada beban malam adalah 3,75%. Selama pengukuran, ditemukan bahwa arus pada penghantar netral sangat besar. Pada beban siang, kerugian pada gardu distribusi 620.CR akibat arus yang mengalir pada penghantar netral adalah sebesar 946,1856 watt pada beban puncak dan memliki nilai ketidakseimbangan beban sebesar 22,02% pada jurusan a dan sebesar 22,42% pada jurusan b. Beberapa cara yang dapat dilakukan untuk mengurangi rugi-rugi ini adalah dengan melakukan pemeliharaan secara rutin dan melakukan penyeimbangan beban pada setiap fasa. Dimana dari hasil simulasi penyeimbangan beban menggunakan aplikasi ETAP 12.6.0 hasil rugi-rugi yang didapat adalah sebesar 0,44% pada jurusan a dan 1,24 % pada jurusan b di mana nilai ini sudah sesuan dengan standar PT.PLN (Persero).

One of the common issues that occur in the distribution network of PT.PLN (Persero) is power losses. The causes of power losses include load imbalance between phases, low power factor, long network distances, and so on. In this study, an analysis of the low voltage network was conducted by calculating its relative power loss. This was done by calculating voltage drop, line resistance, average power loss, and transmitted power to obtain the relative power loss. During the day, the relative power loss of the 620.CR distribution substation is 2.92%, while at night it is 3.75%. During the measurement, it was found that the current in the neutral conductor was very high. In the daytime load, the loss at the 620.CR distribution substation due to the current flowing in the neutral conductor was 946.1856 watts at peak load and had a load imbalance of 22.02% on route A and 22.42% on route B. Some ways to reduce these losses are by performing regular maintenance and balancing the load on each phase. From the results of load balancing simulation using the ETAP 12.6.0 application, the loss results obtained were 0.44% on route A and 1.24% on route B, which are already in accordance with PT.PLN (Persero) standards.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Rugi-rugi daya, Jaringan Tegangan Rendah, Gardu Distribusi Power Losses, Low Voltage Network, Distribution Substation.
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro