ANALISIS PERBAIKAN NILAI TAN DELTA PADA SALURAN KABEL TEGANGAN MENENGAH DENGAN INJECT TEGANGAN DC DI WILAYAH UP3 PONDOK GEDE

Nurjannah, Erny and Hidayat, Syarif (2024) ANALISIS PERBAIKAN NILAI TAN DELTA PADA SALURAN KABEL TEGANGAN MENENGAH DENGAN INJECT TEGANGAN DC DI WILAYAH UP3 PONDOK GEDE. Diploma thesis, ITPLN.

[thumbnail of SKRIPSI 202011207 ERNY NURJANNAH.pdf] Text
SKRIPSI 202011207 ERNY NURJANNAH.pdf
Restricted to Registered users only

Download (5MB)

Abstract

Kondisi SKTM yang lembap dapat menyebabkan berbagai masalah seperti korosi, degradasi isolasi, dan kegagalan listrik. SKTM yang lembap disebabkan adanya uap air yang terperangkap di dalam isolasi. Uap air dianggap sebagai kontaminan karena keberadaannya menyebabkan degradasi material, korosi, serta rugi-rugi dielektrik. Tingginya nilai rugi-rugi dielektrik ditandai dengan nilai Tan Delta yang tinggi pula. 9 Januari 2024 pengujian tan delta pada penyulang Siaga segmen JR220 ke JR22 menunjukkan hasil yang tinggi. Ketika jaringan diaktifkan kembali, terjadi trip yang mengindikasikan adanya masalah pada sistem. Untuk mengidentifikasi sumber masalah tersebut, dilakukanlah proses injeksi tegangan DC. Hasil pengujian Tan Delta disesuaikan dengan standar IEEE 400.2. Setelah dilakukan pengujian Tan Delta, didapatkan kondisi kabel dalam kondisi Action Required karena nilai rata-rata Tan Delta fasa R 69,1, fasa S 68,1 dan fasa T 24,9. Untuk diferensial fasa R 59,3, fasa S 74,6 dan fasa T 17,5. Terakhir, standar deviasi fasa R 3,5, fasa S 2,0 dan fasa T 0,7. Setelah dilakukan proses inject tegangan DC, kondisi kabel dalam kondisi No Action Required karena nilai rata-rata Tan Delta fasa R 0,3, fasa S 0,2 dan fasa T 0,4. Untuk diferensial fasa R dan T 0,1, serta fasa T 0. Terakhir, standar deviasi pada ketiga fasa adalah 0,0.

Moist conditions in Medium Voltage Cable Systems (MVCS) can cause problems such as corrosion, insulation degradation, and electrical failures. Trapped water vapor within the insulation leads to these issues. Water vapor is a contaminant that causes material degradation, corrosion, and dielectric losses, indicated by high Tan Delta values. On January 9, 2024, Tan Delta testing on the Siaga feeder segment JR220 to JR22 showed high results. Upon re-energizing the network, a trip occurred, indicating a system problem. To identify the source, a DC voltage injection process was conducted. Tan Delta test results were evaluated according to IEEE 400.2 standards. Initially, the cable condition was classified as Action Required, with average Tan Delta values of 69.1 for phase R, 68.1 for phase S, and 24.9 for phase T. The differential values were 59.3 for phase R, 74.6 for phase S, and 17.5 for phase T. The standard deviation values were 3.5 for phase R, 2.0 for phase S, and 0.7 for phase T. After the DC voltage injection process, the cable condition improved to No Action Required, with average Tan Delta values of 0.3 for phase R, 0.2 for phase S, and 0.4 for phase T. The differential values were 0.1 for phases R and S, and 0 for phase T, with a standard deviation of 0.0 for all phases.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: SKTM, Tan Delta, Injeksi VDC, TDM62, Rugi-rugi Dielektrik SKTM, Tan Delta, VDC injection, TDM62, Dielectric Losses
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 29 Oct 2025 04:18
Last Modified: 29 Oct 2025 04:18
URI: https://repository.itpln.ac.id/id/eprint/3118