ANALISIS INDIKASI ARUS BOCOR BERDASARKAN PENGUJIAN ISOLASI BELITAN DAN MINYAK PADA TRANSFORMATOR UNIT 2 GIS 150KV PANTAI INDAH KAPUK

Andrianto, Okky Pratama Putra and Fernandes, Alex (2024) ANALISIS INDIKASI ARUS BOCOR BERDASARKAN PENGUJIAN ISOLASI BELITAN DAN MINYAK PADA TRANSFORMATOR UNIT 2 GIS 150KV PANTAI INDAH KAPUK. Diploma thesis, ITPLN.

[thumbnail of SKRIPSI 202011186 OKKY PRATAMA PUTRA ANDRIANTO.pdf] Text
SKRIPSI 202011186 OKKY PRATAMA PUTRA ANDRIANTO.pdf
Restricted to Registered users only

Download (3MB)

Abstract

Transformator Daya merupakan suatu alat listrik statis yang dimana dalamnya terdapat dua buah rangkaian belitan atau lebih, yang dimana secara prinsip kerja yaitu untuk merubah besaran daya yang diberikan pada belitan primer kepada sekunder, baik untuk menaikan ataupun menurunkan tegangan dengan menggunakan Frekuensi yang sama. Pembuatan Skripsi ini bertujuan untuk mengetahui indikasi terjadinya arus bocor dan kondisi kesehatan pada Transformator unit 2 pada GIS 150kV Pantai Indah Kapuk, Penelitian ini menggunakan metode kuantitatif dengan mendapatkan data yang akan diolah dari hasil tahanan isolasi, pengujian tangen delta belitan, dan Tegangan tembus Minyak Transformator, dan dilakukan perhitungan untuk pengolahan data, untuk dari hasil pengujian pada Transformator unit 2 kondisi Transformator terlihat dari hasil nilai Indeks Polarisasi terdapat kondisi “Dipertanyakan” dari hasil uji dengan nilai indeks polarisasi sebesar 1,21, pada hasil tangen delta belitan terdapat hasil titik uji yang tidak sesuai dengan standar yaitu diatas 1% yaitu sebesar 1,663% dan terdapat titik hasil uji yang tidak benar dikarenakan , dan nilai rata - rata kekuatan dielektrik minyak transformator tidak sesuai standar yaitu 39,4kV yang kemudian dilakukan purifikasi sehingga kekuatan dielektriknya menjadi lebih baik yaitu nilai rata -rata kekuatan dielektriknya menjadi sebesar 79,7 kV , dari data hasil uji yang didapatkan bisa dilihat bahwa pada transformator unit 2 GIS 150kV Pantai Indah Kapuk ini terdapat indikasi arus bocor, hal ini dapat dilihat dari hasil pengujian isolasi belitan dan tangen delta belitan yang dimana terdapat nilai dari titik uji yang tidak sesuai standar atau dikatakan bermasalah pada isolasinya yang dimana hal ini memerlukan perbaikan untuk mengurangi dampak buruk yang berlebih terhadap Transformator tersebut.

A Power Transformer is a static electrical device in which there are two or more winding circuits, which in principle works to change the amount of power given to the primary winding to the secondary, either to increase or decrease the voltage using the same frequency. The preparation of this thesis aims to find out the indications of leakage current and health conditions in the Transformer unit 2 on GIS 150kV Pantai Indah Kapuk, This study uses a quantitative method by obtaining data that will be processed from the results of isolation resistance, tangential testing of winding deltas, and Transformer Oil Penetration Voltage, and calculations are carried out for data processing, for the results of testing on Transformer unit 2 the condition of the Transformer can be seen from the results the value of the Polarization Index there is a "Questionable" condition from the test results with a polarization index value of 1.21, in the tangent results of the winding delta there are test points that are not in accordance with the standard, which is above 1%, which is 1.663% and there are test results that are not correct due to , and the average value of the dielectric strength of the transformer oil is not in accordance with the standard, namely 39.4kV which is then purified so that the dielectric strength becomes better, namely the value of The average dielectric strength is 79.7 kV, from the test data obtained it can be seen that in the transformer unit 2 GIS 150kV Pantai Indah Kapuk there is an indication of leakage current, this can be seen from the results of the winding insulation test and the tangent delta of the winding where there is a value from the test point that is not in accordance with the standard or is said to have a problem with the insulation which requires improvement to reduce the excessive adverse impact on the The transformer.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Transformator Daya, Tahanan Isolasi Belitan, Tegangan Tembus, Arus bocor Power Transformer, Winding Insulation Resistance, Break-Through Voltage, Current leakage
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 29 Oct 2025 06:40
Last Modified: 29 Oct 2025 06:40
URI: https://repository.itpln.ac.id/id/eprint/3136