Wati, Sri Handayanipuspita and Hidayat, Syarif (2024) PENGARUH PEMBEBANAN TERHADAP RUGI TOTAL, EFISIENSI DAN SUSUT UMUR TRANSFORMATOR 1 DAN 4 GARDU INDUK 150 KV DURI KOSAMBI. Diploma thesis, ITPLN.
SKRIPSI 202011157 SRI HANDAYANIPUSPITA WATI.pdf
Restricted to Registered users only
Download (4MB)
Abstract
Penelitian ini bertujuan untuk mengetahui pengaruh pembebanan terhadap rugi total, efisiensi dan susut umur transformator 150 kV Duri Kosambi. Pada Gardu Induk 150 kV Duri Kosambi terdapat 5 transformator, dimana peneliti menjadikan tramsformator 1 dan 4 sebagai objek penelitian dikarenakan pembebanan yang tercatat memiliki pembebanan yang besar. Hasil penelitian menunjukkan bahwa pada transformator 1 20kV jam 10.00 WIB memiliki pembebanan sebesar 4 MW dengan rugi tembaga sebesar 1,20 KW dan rugi total sebesar 39,20 KW dengan efisiensi sebesar 96,18%, efisiensi yang menurun dikarenakan pembebanan yang kecil sehingga menyebabkan rugi inti yang lebih besar dibandingkan rugi tembaga dan menghasilkan rugi total yang besar sehingga menurunnya efisiensi. Pembebanan dapat mempengaruhi umur pada transformator, dengan sisa umur transformator 1 sebesar 393,25 tahun dan pada transformator 4 sebesar 200,28 tahun. Pembebanan pada transformator 4 lebih besar dibandingkan dengan transformator 1 sehingga menyebabkan sisa umur transformator 4 lebih singkat.
This research aims to investigate the influence of loading on the total loss, efficiency, and life expectancy of a 150 kV transformer at Duri Kosambi Substation. Among the five transformers at the 150 kV Duri Kosambi Substation, Transformer 1 and 4 were selected as research objects due to their significant recorded loads. The results showed that at 10:00 AM, Transformer 1 with a 20 kV load of 4 MW had a copper loss of 1.20 KW and a total loss of 39.20 KW, resulting in an efficiency of 96.18%. The decrease in efficiency was attributed to the relatively low load, causing core losses to exceed copper losses and leading to higher total losses. Consequently, the efficiency decreased. Loading can affect the lifespan of a transformer, with Transformer 1 having a remaining lifespan of 393.25 years and Transformer 4 having a remaining lifespan of 200.28 years. The higher load on Transformer 4 compared to Transformer 1 resulted in a shorter remaining lifespan for Transformer 4.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Transformator, rugi-rugi transformator, efisiensi transformator, susut umur transformator Transformer, transformer losses, transformer efficiency, transformer lifespan |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 29 Oct 2025 07:37 |
| Last Modified: | 29 Oct 2025 07:37 |
| URI: | https://repository.itpln.ac.id/id/eprint/3153 |