Intansari, Meisin Tia and Diantari, Retno Aita (2024) EVALUASI KINERJA SISTEM PROTEKSI TERHADAP SAMBARAN PETIR PADA GARDU INDUK PT.PLN CIANJUR DENGAN IMPLEMENTASI TEKNOLOGI LIGHTNING ARRESTER. Diploma thesis, ITPLN.
SKRIPSI 202011152 MEISIN TIA INTANSARI.pdf
Restricted to Registered users only
Download (3MB)
Abstract
Keefektifan dari Ligthning Arrester sesuai dari SPLN 1978 dimana jarak minimal dari Lightning Arrester terhadap Transformator Daya adalah 3m dan jarak maksimalnya adalah 80m. Keefektifan dari Lightning Arrester juga diihat dari nilai tegangan pengenal apakah sudah sesuai dengan tegangan pasang pada arrester yang nantinya mempengaruhi nilai tegangan nominalnya. Dimana pada fungsi Lightning Arrester sendiri yang nilai tegangan pengenalnya mempengaruhi nilai efektif dari kerja LA, Pada penelitian ini metode yang digunakan adalah metode analisa dengan pengujian penempatan jarak arrester yang dimulai dari jarak 15m hingga 75m. Dimana dalam perhitungan jarak penempatan Lightning Arrester di Gardu Induk Cianjur dengan jarak maksimum yang didapat adalah 45m dengan kapasistas nilai tegangan nominalnya adalah 650kV. Nilai tegangan yang telah masuk kedalam transformator bila nilainya dibawah BIL (Basic Insulation Level) dikatakan tidak efektif dan pada data penelitian ini adalah nilainya sudah sesuai dengan BIL Karena pada GI Cianjur nilai daya nya adalah 460kV. Sehingga perlindungan terhadap sambaran petir dari peralatan yang baik sesuai dengan SPLN adalah 3meter. Jarak tersebut sesuai dengan penentuan BIL (Basic Insulation Level) dari peralatan yang dilindungi yaitu transformator daya dan pengaruh dari tegangan kerja dari arrester itu sendiri. Dimana apabila BIL dari peralatan yang dilindungi semakin besar maka akan diperoleh nilai jarak maksimum penempatan arrester akan semakin besar juga.
The effectiveness of the Lightning Arrester is in accordance with SPLN 1978 where the minimum distance from the Lightning Arrester to the Power Transformer is 3m and the maximum distance is 80m. The effectiveness of the Lightning Arrester is also seen from the rated voltage value whether it is in accordance with the installed voltage on the arrester which will later affect the nominal voltage value. Where in the function of the Lightning Arrester itself, the rated voltage value affects the effective value of the LA work, In this study the method used is the analysis method by testing the placement of the arrester distance starting from a distance of 15m to 75m. Where in the calculation of the placement distance of the Lightning Arrester at the Cianjur Substation with the maximum distance obtained is 45m with a nominal voltage capacity of 650kV. The voltage value that has entered the transformer if the value is below the BIL (Basic Insulation Level) is said to be ineffective and in this research data the value is in accordance with the BIL because at the Cianjur GI the power value is 460kV. So that the protection against lightning strikes from good equipment according to SPLN is 3 meters. This distance is in accordance with the determination of the BIL (Basic Insulation Level) of the protected equipment, namely the power transformer and the influence of the working voltage of the arrester itself. Where if the BIL of the protected equipment is greater, the maximum distance value for placing the arrester will also be greater.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Ligthtning Arrester, Sistem Ptoteksi, BIL Lightning Arrester, Protection System, BIL |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 03 Nov 2025 02:33 |
| Last Modified: | 03 Nov 2025 02:33 |
| URI: | https://repository.itpln.ac.id/id/eprint/3254 |