ANALISIS PENGARUH KETIDAKSEIMBANGAN BEBAN TERHADAP RUGI-RUGI PADA PENGHANTAR NETRAL GARDU DISTRIBUSI PT PLN (PERSERO) UP3 CIKOKOL

Erdami, Rayhan and Hajar, Ibnu (2024) ANALISIS PENGARUH KETIDAKSEIMBANGAN BEBAN TERHADAP RUGI-RUGI PADA PENGHANTAR NETRAL GARDU DISTRIBUSI PT PLN (PERSERO) UP3 CIKOKOL. Diploma thesis, ITPLN.

[thumbnail of SKRIPSI 202011136 RAYHAN ERDAMI.pdf] Text
SKRIPSI 202011136 RAYHAN ERDAMI.pdf
Restricted to Registered users only

Download (4MB)

Abstract

Ketidakseimbangan beban pada transformator merupakan kondisi yang terjadi akibat beban pada fasa R, fasa S dan fasa T tidak merata. Ketidakseimbangan beban sering terjadi di jaringan distribusi listrik, khususnya pada gardu distribusi yang melayani berbagai jenis beban dengan karakteristik berbeda. Dengan kondisi tersebut mengakibatkan mengalirnya arus pada penghantar netral yang mengakibatkan adanya rugi-rugi daya pada penghantar netral. Pada penelitian ini membahas rugi-rugi daya pada penghantar netral akibat ketidakseimbangan beban transformator. Berdasarkan penelitian yang telah dilaksanakan, diketahui bahwa besarnya rugi-rugi daya pada penghantar netral pada siang hari sebelum dilakukan penyeimbangan beban rata-rata sebesar 50904,13 Watt atau 13,12% dan pada malam hari sebelum dilakukan penyeimbangan beban rata-rata sebesar 68922,51 Watt atau 17,76%. Kemudian setelah dilakukan penyeimbangan beban, rugi-rugi daya pada penghantar netral pada siang hari bernilai 793,40 Watt atau 0,20%, dan rugi-rugi daya pada penghantar netral pada malam hari bernilai 895,38 Watt atau 0,23%. Hasil tersebut telah sesuai dengan standar SPLN yaitu <5%.

Load imbalance in the transformer is a condition that occurs due to uneven loads on phase R, phase S and phase T. Load imbalance often occurs in electricity distribution networks, especially in distribution substations that serve various types of loads with different characteristics. With these conditions resulting in the flow of current in the neutral conductor which results in power losses in the neutral conductor. This research discusses power losses in the neutral conductor due to transformer load imbalance. Based on the research that has been carried out, it is known that the amount of power loss on the neutral conductor during the day before load balancing is carried out averages 50904.13 Watt or 13.12% and at night before load balancing is carried out averages 68922.51 Watt or 17.76%. Then after load balancing, the power loss at the neutral conductor during the day is 793.40 Watt or 0.20%, and the power loss at the neutral conductor at night is 895.38 Watt or 0.23%. These results are in accordance with the SPLN standard of

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Transformator, Ketidakseimbangan Beban, Rugi-rugi, Arus Netral Transformer, Load Unbalance, Loss, Neutral Current
Subjects: Skripsi
Bidang Keilmuan > Teknik Elektro
Divisions: Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro
Depositing User: Sudarman
Date Deposited: 03 Nov 2025 02:55
Last Modified: 03 Nov 2025 02:55
URI: https://repository.itpln.ac.id/id/eprint/3260

Actions (login required)

View Item
View Item