Abstract
Kubikel ACO secara otomatis dan melakukan perpindahan selama 0,2 detik ketika terjadi kehilangan tegangan di penyulang utama pada prinsip kubikel ACO pada pelanggan premium yaitu menerima pasokan listrik dari dua penyulang, penyulang utama dan penyulang cadangan. Jika ada kendala atau gangguan pada pasokan utama, pasokan cadangan akan memberikan pasokan ke gardu distribusi pelanggan premium.Pada penerpan ACO harus memiliki 2 penyulang yaitu penyulang utama dan penyulang cadangan konfigurasi spindel yang dimana dianggap handal karena terdiri dari dua penyulang utama (working feeder) berfungsi sebagai penyulang utama dan penyulang ekspres berfungsi sebagai penyulang cadangan. Penyulang operasi berfungsi sebagai sumber pasokan utama ke pelanggan, dan penyulang ekspres berfungsi sebagai pasokan cadangan apabila terjadi gangguan. Kontinyuitas penyediaan listrik dapat meningkatkan kebisingan dan mengurangi durasi pemadaman pelanggan. Kubikel ACO dapat dipindahkan dari suplai utama ke suplai cadangan selama pengujian dengan waktu 0,2 detik untuk memindahkan ACO. Meningkatkan dan mengurangi pemadaman pada pelanggan. Setelah penggunaan ACO nilai indeks SAIDI, SAIFI dan CAIDI menurunkan pemadaman nya, yang dimana pada SAIDI sebesar 315 menit/pelangan/tahun dan 420 menit/pelangan/tahun setelah diterapkan ACO sebesar 0,4 menit/pelangan/tahun dan 0,8 menit /pelanggan/tahun dan pada SAIFI jumlah pemadan pengurangan yang dimana pada 2 gardu sebelum dipasang ACO sebesar 5 kali/pelanggan/tahun dan 9 kali/pelanggan/tahun dan sesudahnya di terapkan ACO 2 kali/pelanggan/tahun dan 4 kali/pelanggan/ tahun serta pada CAIDI yaitu sebelum menerapkan ACO sebesar 63 menit/kali dan 46,6 menit/kali sedangkan sudah diterapkan ACO jumlah berkurang sebesar 0,2 detik/kali dan 0,2 detik/kali.6.
The working ACO cubicle will work automatically and make a shift for 0.2 seconds when there is a loss of voltage at the main feeder according to the ACO cubicle principle for premium customers, namely receiving electricity supply from two feeders, the main feeder and the backup feeder. If there is a problem or disruption to the main supply, the backup supply will provide supply to the premium customer distribution substation. In ACO applications, it must have 2 feeders, namely the main feeder and the spindle configuration backup feeder which is considered reliable because it consists of two main feeders (working feeders) that function as the main feeder and the express feeder functions as a backup feeder. The operating feeder functions as the main source of supply to customers, and the express feeder functions as a backup supply in the event of a disruption. Continuous electricity supply can improve noise and reduce the duration of customer outages. The ACO cubicle can be moved from the primary supply to the backup supply during testing with a 0.2 second time to move the ACO. Increase and reduce customer outages. After using ACO, the index values of SAIDI, SAIFI and CAIDI reduce outages, which in SAIDI is 315 minutes/customer/year and 420 minutes/customer/year after implementing ACO it is 0.4 minutes/customer/year and 0.8 minutes/year. customers/year and at SAIFI the number of matching reductions in the 2 substations before ACO was installed was 5 times/customer/year and 9 times/customer/year and after that ACO was applied 2 times/customer/year and 4 times/customer/year and in CAIDI, namely before implementing ACO it was 63 minutes/time and 46.6 minutes/time, whereas after implementing ACO the number decreased by 0.2 seconds/time and 0.2 seconds/time.
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | ACO Kubikel, Keandalan,Saidi,Saifi,Caidi ACO Cubicle, Reliability,Saidi,Saifi,Caidi |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 03 Nov 2025 02:55 |
| Last Modified: | 03 Nov 2025 02:55 |
| URI: | https://repository.itpln.ac.id/id/eprint/3261 |