Fauzi, Abi Adnan and Pasra, Nurmiati (2024) ANALISIS UNJUK KERJA DAN PREDIKSI UMUR TRANSFORMATOR DENGAN METODE HEALTH INDEX PADA GARDU INDUK 150 KV DI PT PLN (PERSERO) KARET LAMA. Diploma thesis, ITPLN.
SKRIPSI 202011086 ABI ADNAN FAUZI.pdf
Restricted to Registered users only
Download (6MB)
Abstract
Transformator yang digunakan di Gardu Induk Karet Lama memiliki kondisi rata-rata beban berada diatas 46 MVA atau 78 % dari kapasitas maksimalnya. Beban tertinggi dicapai oleh transformator 2 pada bulan November dan Desember 2023 dengan beban sebesar 56 MW atau 93% dari kapasitas maksimal. Hasil pengujian tangen delta bushing transformator menunjukkan nilai tangen delta lebih dari 1%, melebihi standar SKDIR 5020 (IEC 60137 – DF tan δ). Oleh karena itu, bushing fasa S perlu diganti segera. Tindakan pemeliharaan dilakukan penggantian bushing.Hasil pengujian tangen delta menunjukkan bahwa sebelum penggantian, nilainya sebesar 1,3225%, sedangkan setelah penggantian turun menjadi 0,2933%. Dalam penelitian ini, Metode Health Index digunakan untuk menganalisis kondisi dan memprediksi umur transformator. Parameterparameter yang diamati dan dinilai meliputi faktor historis yang terkait dengan pengamatan operasional dan faktor kondisi yang terkait dengan pengujian bagian-bagian transformator. Hasil penelitian menunjukkan nilai Health Index transformator 1 sebesar 2,18 untuk prediksi sisa umur beroperasi 5 sampai dengan 10 tahun. Transformator 2 memiliki nilai Health Index sebesar 2,72, prediksi sisa umur beroperasi 5 sampai dengan 10 tahun, sedangkan transformator 3 memiliki nilai Health Index sebesar 3,17, prediksi sisa umur beroperasi lebih dari 15 tahun. Dengan demikian, penelitian ini menunjukkan bahwa transformator di Gardu Induk Karet Lama memerlukan perawatan dan perbaikan segera untuk meningkatkan kinerja dan meningkatkan umur beroperasi."
The transformers used at the Karet Lama substation have an average load condition of above 46 MVA or 78% of their maximum capacity. The highest load was achieved by transformer 2 in November and December 2023 with a load of 56 MW or 93% of maximum capacity. The transformer bushing delta tangent test results show a delta tangent value of more than 1%, exceeding the SKDIR 5020 standard (IEC 60137 – DF tan δ). Therefore, the S phase bushing needs to be replaced immediately. The maintenance action was to replace the bushing. The results of the tangent delta test showed that before replacement, the value was 1.3225%, while after replacement it fell to 0.2933%. In this research, the Health Index method is used to analyze the condition and predict the life of the transformer. The parameters observed and assessed include historical factors related to operational observations and condition factors related to testing transformer parts. The research results show that the Health Index value for transformer 1 is 2.18 to predict the remaining operating life of 5 to 10 years. Transformer 2 has a Health Index value of 2.72, predicted remaining operating life of 5 to 10 years, while transformer 3 has a Health Index value of 3.17, predicted remaining operational life of more than 15 years. "Thus, this research shows that the transformers at the Old Karet Substation require immediate maintenance and repair to improve performance and increase operating life."
| Item Type: | Thesis (Diploma) |
|---|---|
| Uncontrolled Keywords: | Faktor Historis,Faktor Kondisi,Heath Index,Pembebanan,Tangen delta, Umur Transformator Historical Factors, Condition Factors, Health Index, Loading,Delta tangent, Transformer Age |
| Subjects: | Skripsi Bidang Keilmuan > Teknik Elektro |
| Divisions: | Fakultas Ketenagalistrikan dan Energi Terbarukan > S1 Teknik Elektro |
| Depositing User: | Sudarman |
| Date Deposited: | 03 Nov 2025 08:14 |
| Last Modified: | 03 Nov 2025 08:14 |
| URI: | https://repository.itpln.ac.id/id/eprint/3299 |